User Manual
Load specifications
N 536D31 N 536D51
Type
Service life
Mechanical service life (operating cycles in millions) 1
Electrical service life (operating cycles in millions) 0.1
Power loss
Maximum power loss per device at rated output [W]** 7 12
Switching capacities/load types, loads
Resistive load [W]* 3680
Minimum switching capacity [V/mA] 12/100
Maximum DC1 breaking capacity [V/A] 24/10
Incandescent lamps
Incandescent lamp [W]* 2500
Halogen lamp 230 V [W]* 2500
NV halogen lamp with mechanical transformer [VA] 500
Outputs (control outputs, 1…10 V)
Number of control voltage outputs DC 1...10 V (passive) 4 8
Maximum current per control output [mA]* 106 94
Control output, max. number of ECGs & drivers (2 mA per EVG)* 53 47
* Restrictions for rated current (device) and derating information:
• 16 A resistive in switching actuator mode; dimming current = 0 mA; independent of installation position and temperature
• 10 AX is switching/dimming actuator mode; dimming current = 106 mA max. (N 536D31), 94 mA max. (N 536D51)
with standard installation position and + 25 °C
• 10 AX is switching/dimming actuator mode; dimming current = 84 mA max. (N 536D31), 74 mA max. (N 536D51)
with standard installation position and + 45 °C