Point Database
Siemens Building Technologies, Inc. 6-3
Address Descriptor Application Description
32 OCC SUP MIN 2601, 2603, 2611,
2613
Minimum supply in occupied mode.
36 FLOW COEFF 1 2600 Calibration parameter for airflow sensor.
36 SUP FLO COEF 2601, 2603, 2611,
2613
Calibration parameter for airflow sensor.
36 SUP1 COEF 2602, 2612 Calibration parameter for airflow sensor.
37 DIF ALM ENA 2601, 2602, 2603,
2611, 2612, 2613
When this is set to “yes”, the VOL DIF ALM point can drive ALARM
DO8.
38 DIF ALM LVL 2601, 2602, 2603,
2611, 2612, 2613
VOL DIF ALM is triggered when VOL DIFFRNC goes below this level.
39 DIF ALM DEL 2601, 2602, 2603,
2611, 2612, 2613
Alarm delay point to prevent “nuisance alarms” on the flow difference.
40 FAIL MODE 2601, 2602, 2603,
2611, 2612, 2613
Select “HOLD” or “CLOSE” to tell the supply damper(s) what to do
when a flow measurement signal is lost.
{41} DO1 2600
{41} SUP FILL DO1 2601, 2603 Drives a solenoid valve that moves a damper. Do not use or manually
set this point.
{41} SUP1 FILL DO1 2602 Drives a solenoid valve that moves a damper. Do not use or manually
set this point.
{41} SUP EXTN DO1 2611, 2613 Drives a LAB AO-E module to extend electronic actuator. Do not use or
manually set this point.
{41} SUP1 ETN DO1 2612 Drives a LAB AO-E module to extend electronic actuator. Do not use or
manually set this point.
{42} DO 2 2600
{42} SUP BLED DO2 2601, 2603 Drives a solenoid valve that moves a damper. Do not use or manually
set this point.
{42} SUP1 BLD DO2 2602 Drives a solenoid valve that moves a damper. Do not use or manually
set this point.
{42} SUP RETC DO2 2611, 2613 Drives a LAB AO-E module to retract electronic actuator. Do not use or
manually set this point.
{42} SUP1 RTC DO2 2612 Drives a LAB AO-E module to retract electronic actuator. Do not use or
manually set this point.
{43} DO3 2600
{43} GEX FILL DO3 2601, 2603 Drives a solenoid valve that moves a damper. Do not use or manually
set this point.
{43} SUP2 FIL DO3 2602 Drives a solenoid valve that moves a damper. Do not use or manually
set this point.
continued on the next page. . .
{43} GEX EXTN DO3 2611, 2613 Drives a LAB AO-E module to extend electronic actuator. Do not use or
manually set this point.
{43} SUP2 ETN DO3 2612 Drives a LAB AO-E module to extend electronic actuator. Do not use or
manually set this point.