Operating Instructions
Siemens Building Technologies, Inc. 6-1
6
Point Database
Chapter 6 presents a description of the point database for Applications 2600 (Slave Mode)
and pneumatic actuator Applications 2601, 2602, and 2603 as well as electronic actuator
Applications 2611, 2612, and 2613, including point descriptors, point addresses, and a listing
of applications in which each point is found.
Address Descriptor Application Description
01 CTLR ADDRESS 2600, 2601, 2602,
2603, 2611, 2612,
2613
Identifies the controller on the LAN trunk.
02 APPLICATION 2600, 2601, 2602,
2603, 2611, 2612,
2613
Identification number of the program running in the controller.
{04} ROOM TEMP 2600, 2601, 2602,
2603, 2611, 2612,
2613
Actual reading from the room temperature sensor.
05 CFLO START 2601, 2603, 2611,
2613
Point used to set up the temperature control sequence.
06 CFLO END 2601, 2603, 2611,
2613
Point used to set up the temperature control sequence.
07 REHEAT START 2601, 2602, 2611,
2612
Point used to set up the temperature control sequence.
07 HFLO START 2603, 2613 Point used to set up the temperature control sequence.
08 REHEAT END 2601, 2602, 2611,
2612
Point used to set up the temperature control sequence.
08 HFLO END 2603, 2613 Point used to set up the temperature control sequence.
{09} TEMP CTL VOL 2601, 2603, 2611,
2613
Amount of supply airflow that the temperature control sequence
determines is necessary to regulate the room temperature.
10 HFLO MAX 2603, 2613 Point used to set up the heating mode of a dual duct temperature
control sequence.
continued on the next page. . .
12 BUTTON ENA 2601, 2602, 2603,
2611, 2612, 2613
Connects Point 25 to Point 45. If this point is disabled, the button does
not affect occupancy.
{13} ROOM STPT 2600,2601, 2602,
2603, 2611, 2612,
Desired value of the room temperature.