Operating Instructions
Point Database
Siemens Building Technologies, Inc. 6-3
Descriptor Address Application Description
HORN SILENCE 61 651 Indicates if the first button (labeled “Horn Silence”) has
been pressed.
If no alarm condition is present, then the state of the point remains
at OFF.
If an alarm exists, then the horn will silence and the status will
change to ON.
When the alarm condition clears, the point will reset to OFF.
AUX BUTTON 1 62 651 The hardware input, point BUTTON 2 (Point 57), is logically tied to
this point. When the operator presses the point BUTTON 2, the
application toggles the status of this output. This point is available
for field panel use.
AUX BUTTON 2 63 651 The hardware input, point BUTTON 3 (Point 58), is logically tied to
this point. When the operator presses the point BUTTON 3, the
application toggles the status of this output. This point is available
for field panel use.
EMERGENCY 64 651 Indicates if the fourth (last) button on the FHM has been pressed.
This is a toggle action digital input; when pressed, the status of this
point is ALARM. If pressed again, then the status of this point is
NORMAL. The LCD segment “USER ALARM” will light when the
status of the point is ALARM (refer to Point 7).
MIN RAW 71 651 Represents the field calibration min raw reading of the sensor. The
min raw reading is gound by observing the raw value when the
sash is moved to a min calibration sash position.
MID RAW 73 651 Represents the field calibration mid raw reading of the sensor. The
mid raw reading is gound by observing the raw value when the
sash is moved to a mid calibration sash position.
MAX RAW 75 651 Represents the field calibration max raw reading of the sensor.
The max raw reading is gound by observing the raw value when
the sash is moved to a max calibration sash position.
CAL REQUEST 80 651 The installer sets this point to YES to initiate the field calibration
procedure. When calibration is complete, the installer sets the
point CAL COMPLETE (Point 87) to YES to complete the transfer
of entered data into EEPROM.
NOTE: Data entered into calibration values is
not
saved until CAL
COMPLETE is set to YES. If the installer starts the calibration
procedure and desires
not
to continue with the calibration, then
changing the point CAL REQUEST to NO before changing the
point CAL COMPLETE to YES will abort the calibration operation.
Calibration data will not be saved.
MAX FVEL 81 651 Represents the field calibration maximum face velocity. The
maximum face velocity is found using the portable velocity probe
and moving the sash to a maximum calibration velocity position.
MAX DONE 82 651 The person performing calibration toggles this point to save the
entered maximum velocity calibration value to EEPROM.
continued on the next page. . .