Operating Instructions

Fume Hood Monitor Owner's Manual
5-2 Siemens Building Technologies, Inc.
Point database
The following table contains all of the points in Application 650.
Table 5-1. Point Database for Fume Hood Monitor Application 650.
Point
Number
Descriptor Factory
Default
(SI units)
Engr. Units
(SI units)
Slope
(SI units)
Intercept
(SI units)
On Text Off Text
1 CTLR ADDRESS 99 -- 1 0 -- --
2 APPLICATION 650 -- 1 0 -- --
{4} FACE VEL -- FPM
(MPS)
1 0 -- --
{8}GEN FAILURE OFF -- -- -- ON OFF
{29} OCC UNOCC OCC -- -- -- UNOCC OCC
{41} ALARM RELAY NORMAL -- -- -- NORMAL ALARM
{55} AUX DI OPEN -- -- -- CLOSED OPEN
{56} BUTTON 1
(refer to NOTE 3)
OPEN -- -- -- CLOSED OPEN
{57} BUTTON 2
(refer to NOTE 3)
OPEN -- -- -- CLOSED OPEN
{58} BUTTON 3
(refer to NOTE 3)
OPEN -- -- -- CLOSED OPEN
{59} BUTTON 4
(refer to NOTE 3)
OPEN -- -- -- CLOSED OPEN
88 CAL RAW -- -- 1 0 -- --
91 BLANK DISP OFF -- -- -- ON OFF
92 DISPLAY RES 10
(0.05)
FPM
(MPS)
1 0 -- --
93 ENGUNITS ENG -- -- -- SI ENG
94 LAMP TEST OFF -- -- -- ON OFF
95 DISPLAY WT 100 PCT 0.4 0.0 -- --
{99} ERROR STATUS
(refer to NOTE 3)
0----------
1. Points not shown in this table are not used with this application.
2. One value listed in a column indicates that the value is the same in English as it is in SI units.
3. Points represent hardware inputs and are used by the FHM firmware only.
4. Point numbers that appear in brackets {}may be unbundled at the field panel.