Point database
The following table contains all of the points in Application 651. Calibration Report points are
numbered in the 80s. Set-up Report points are numbered in the 90s.
Table 4-1. Point Database for Fume Hood Monitor Application 651.
Point
Number
Descriptor Factory
Default
(SI units)
Engr. Units
(SI units)
Slope
(SI units)
Intercept
(SI units)
On Text Off Text
1 CTLR ADDRESS 99 -- 1 0 -- --
2 APPLICATION 651 -- 1 0 -- --
{4} FACE VEL -- FPM (MPS) 1 0 -- --
{5} LOW ALM OFF -- -- -- ON OFF
{6} HIGH ALM OFF -- -- -- ON OFF
{7} ALARM STATUS NORMAL -- -- -- ALARM NORMAL
{8} GEN FAILURE OFF -- -- -- ON OFF
{10} HI ALM LMT 255 (1.28) FPM (MPS) 1 0 -- --
{13} LO ALM LMT 0 FPM (MPS) 1 0 -- --
{29} OCC UNOCC OCC -- -- -- UNOCC OCC
{41} ALARM RELAY NORMAL -- -- -- ALARM NORMAL
52 DI FUNCTION 0 -- 1 0 -- --
{53} SASH ALARM NORMAL -- -- -- ALARM NORMAL
54 SASH TIME 120 SEC 1 0 -- --
{55} AUX DI OPEN -- -- -- CLOSED OPEN
{56} BUTTON 1
(refer to NOTE 3)
OPEN -- -- -- CLOSED OPEN
{57} BUTTON 2
(refer to NOTE 3)
OPEN -- -- -- CLOSED OPEN
{58} BUTTON 3
(refer to NOTE 3)
OPEN -- -- -- CLOSED OPEN
{59} BUTTON 4
(refer to NOTE 3)
OPEN -- -- -- CLOSED OPEN
{61} HORN SILENCE OFF -- -- -- ON OFF
{62} AUX BUTTON 1 OFF -- -- -- ON OFF
{63} AUX BUTTON 2 OFF -- -- -- ON OFF
{64} EMERGENCY NORMAL -- -- -- ALARM NORMAL
1. Points not shown in this table are not used with this application.
2. One value listed in a column indicates that the value is the same in English as it is in SI units.
3. Points represent hardware inputs and are used by the FHM firmware only.
4. Point numbers that appear in brackets {}may be unbundled at the field panel.
continued on the next page. . .