Operating Instructions

Siemens Building Technologies, Inc. 4-1
4
Application 651 Operating Mode
Chapter 4 describes the Application 651 Operating Mode available in the FHM.
The FHM may be stand-alone or connected to a field panel. The FHM can also send an
alarm notification to a centralized control system. Table 4-1 contains Operating Mode point
database information.
Overview
Application 651 is one of two FHM applications. This application is the Operating Mode,
which determines the features that are available to the user.
Occupied/unoccupied mode
Application 651 is capable of using two modes, occupied and unoccupied, set the application
to the appropriate mode using OCC UNOCC (Point 29).
The occupied mode is the most common Operating Mode. In occupied mode, the FHM does
the following:
Detects alarms
Displays face velocity
Allows the user to initiate an EMERGENCY alarm
The unoccupied mode is controlled from the field panel, AUX DI, or the AUX 2 button as
defined by DI FUNCTION (Point 52) and is typically used when the FHM is not needed for
monitoring alarm conditions.
If
Then
The FHM displays
OCC UNOCC is set to UNOCC the red LED illuminates, and
the green LED turns OFF, and
the FHM will not annunciate
alarms.
OFF, and will not display face
velocity.