Application
Table Of Contents
Point Database Application 2900
18
Siemens Industry, Inc. Application Note, App 2940 140-1317
Restricted 2015-11-04
Point Database Application 2900
Point
Number
a),
b)
Descriptor
Factory
Default
(SI Units)
c)
Eng Units
(SI Units)
c)
Slope
(SI Units)
c)
Intercept
(SI Units)
c)
On Text
Off Text
1 CTLR ADDRESS 99 -- 1 0 -- --
2 APPLICATION 2900 -- 1 0 -- --
{36} AVS2 PRESS 0.0 (0.0) IN H2O
(K PA)
0.0001
(0.000025)
0 -- --
{37} DI 2 OFF -- -- -- ON OFF
{38} DI 6 OFF -- -- -- ON OFF
{39} AO 1 0 VOLTS 0.01 0 -- --
{40} AO 3 0 VOLTS 0.01 0 -- --
{41} DO 1 OFF -- -- -- ON OFF
{42} DO 2 OFF -- -- -- ON OFF
{43} DO 3 OFF -- -- -- ON OFF
{44} DO 4 OFF -- -- -- ON OFF
{45} DO 5 OFF -- -- -- ON OFF
{46} DO 6 OFF -- -- -- ON OFF
{47} DO 7 OFF -- -- -- ON OFF
{48} DO 8 OFF -- -- -- ON OFF
{49} AI 3 0 VOLTS 0.01 0 -- --
{50} AI 4 0 VOLTS 0.001 0 -- --
{51} AI 5 0 KOHM 0.01 0 -- --
{89} AO2 0 VOLTS 0.01 0 -- --
{97} AVS1 PRESS 0.0 (0.0) IN H2O
(K PA)
0.0001
(0.000025)
0 -- --
{99} ERROR STATUS 0 -- 1 0 -- --
a)
Points not listed are not used in this application.
b)
Point numbers that appear in brackets { } may be unbundled at the field panel.
c)
A single value in a column means that the value is the same in English units and in SI units.