Application

Point Database Application 2940
16
Siemens Industry, Inc. Application Note, App 2940 140-1317
Restricted 2015-11-04
Point
Number
a),
b)
Descriptor
Factory
Default
(SI Units)
c)
Eng Units
(SI Units)
c)
Slope
(SI Units)
c)
Intercept
(SI Units)
c)
On Text
Off Text
{42} RETC DO2 RETC -- -- -- HOLD RETC
{43} DO 3 OFF -- -- -- ON OFF
{44} DO 4 OFF -- -- -- ON OFF
{45} HI.LOW DO5 HI -- -- -- LO HI
{46} DECOM DO6 OFF -- -- -- ON OFF
{47} ALARM DO7 OFF -- -- -- ON OFF
{48} AUTOZERO DO8 OFF -- -- -- ON OFF
{49} AI 3 0 VOLTS 0.01 0 -- --
{50} AI 4 0 VOLTS 0.001 0 -- --
{51} AI 5 0 KOHM 0.01 0 -- --
{56} DI 4 OFF -- -- -- ON OFF
{58} DMPR CMD -100 PCT 1 -100 -- --
59 INVERT DO2 YES -- -- -- YES NO
60 AVS FAILMODE OPEN -- -- -- OPEN HOLD
61 EXH P GAIN 0.04 -- 0.001 0 -- --
62 EXH I GAIN 0 -- 0.001 0 -- --
63 EXH D GAIN 0 -- 0.001 0 -- --
{78} STARTUP DI4 NO -- -- -- YES NO
{80} EXH HI STPT 3500
(1651.65)
CFM ( LPS) 4 (1.8876) 0 -- --
{81} EXH LO STPT 192
(90.6048)
CFM ( LPS) 4 (1.8876) 0 -- --
{82} EXH STPT 0 (0.0) CFM ( LPS) 4 (1.8876) 0 -- --
{89} EXH SIG AO2 0 VOLTS 0.01 0 -- --
90 AO2 RANGE 0 (0.0) CFM ( LPS) 4 (1.8876) 0 -- --
91 AO2 DEADBAND 5.2 PCT 0.4 0 -- --
92 AO2 V MIN 1 VOLTS 0.01 0 -- --
{94} CAL AIR NO -- -- -- YES NO
95 CAL SETUP 4 -- 1 0 -- --
96 CAL TIMER 12 HRS 1 0 -- --
{97} AVS1 PRESS 0.0 (0.0) IN H2O
(K PA)
0.0001
(0.000025)
0 -- --
98 LOOP TIME 0.1 SEC 0.1 0 -- --
{99} ERROR STATUS 0 -- 1 0 -- --
106 DISPLAY WT 100 PCT 0.4 0 -- --
107 DISPLAY RES 20 (9.438) CFM ( LPS) 4 (1.8876) 0 -- --
108 BLANK DSPLY OFF -- -- -- ON OFF