Application
Table Of Contents
Point Database Application 2940
15
Siemens Industry, Inc. Application Note, App 2940 140-1317
Restricted 2015-11-04
Point Database Application 2940
Point
Number
a),
b)
Descriptor
Factory
Default
(SI Units)
c)
Eng Units
(SI Units)
c)
Slope
(SI Units)
c)
Intercept
(SI Units)
c)
On Text
Off Text
1 CTLR ADDRESS 99 -- 1 0 -- --
2 APPLICATION 2900 -- 1 0 -- --
{05} LOW ALM OFF -- -- -- ON OFF
{06} HIGH ALM OFF -- -- -- ON OFF
{07} EMER ALM OFF -- -- -- ON OFF
{08} GEN FAILURE OFF -- -- -- ON OFF
10 HI ALM LMT 150 PCT 1 0 -- --
11 HI WARN LMT 135 PCT 1 0 -- --
12 LOW WARN LMT 85 PCT 1 0 -- --
13 LOW ALM LMT 70 PCT 1 0 -- --
14 EMER TIMER 300 SEC 1 0 -- --
15 EMER STPT 150 PCT 1 0 -- --
{16} LOW WARN OFF -- -- -- ON OFF
{17} HIGH WARN OFF -- -- -- ON OFF
18 ALARM TIME 5 SEC 1 0 -- --
{19} ALM AKNLG OFF -- -- -- ON OFF
{20} OCC.UNOCC OCC -- -- -- UNOCC OCC
{21} STARTUP MODE 3 -- 1 0 -- --
{22} ODP STPT SW HI -- -- -- LO HI
{23} RIGHT SWITCH OFF -- -- -- ON OFF
{31} EXH VOL 0 (0.0) CFM ( LPS)
4 (1.8876) 0 -- --
32 FLOW COEF 0.73 -- 0.01 0 -- --
33 DUCT AREA 0.55
(0.051106)
SQ. FT
(SQ M)
0.025
(0.002323)
0 -- --
34 TRANS RANGE 0.0 (0.0) IN H2O
(K PA)
0.0001
(0.000025)
0 -- --
35 LINEAR FL RG 0 (0.0) CFM ( LPS)
4 (1.8876) 0 -- --
{36} AVS2 PRESS 0.0 (0.0) IN H2O
(K PA)
0.0001
(0.000025)
0 -- --
{37} DI2 STPT SW HI -- -- -- LO HI
{38} DI 6 OFF -- -- -- ON OFF
{39} AO 1 0 VOLTS 0.01 0 -- --
{40} AO 3 0 VOLTS 0.01 0 -- --
{41} EXTN DO1 HOLD -- -- -- EXTN HOLD