Data Sheet for Product

Siemens Industry, Inc. Page 9 of 13
Unit Size 112
1-Row Coil
Airflow, CFM
400 600 800 1400
GPM Heating Capacity (MBH)
Waterside
Head Loss
(ft. wg.)
2 17.9 21.5 24.1 29.4 0.55
3 18.8 22.9 25.9 32.2 1.21
4 19.4 23.7 27 33.9 2.11
5 19.7 24.2 27.7 35.0 3.24
6 20.0 24.6 28.1 35.7 4.61
7 20.1 24.8 28.5 36.3 6.22
9 20.4 25.2 29 37.1 10.11
10 20.5 25.3 29.2 37.4 12.40
Air Side Pressure Drop (Inches WC)
0.02 0.04 0.07 0.19
Unit Size 210
1-Row Coil
Airflow, CFM
500 800 1200 1800
GPM Heating Capacity (MBH)
Waterside
Head Loss
(ft. wg.)
1 20.0 23.8 26.9 29.9 0.20
2 23.4 28.9 33.8 38.8 0.76
3 24.8 31.1 36.9 43.0 1.65
4 25.6 32.4 38.8 45.6 2.87
5 26.1 33.2 40.0 47.2 4.41
6 26.4 33.7 40.8 48.4 6.26
8 26.9 34.5 41.9 50.0 10.92
10 27.2 35.0 42.6 51.1 16.8
Air Side Pressure Drop (Inches WC)
0.02 0.04 0.08 0.15
Unit Size 212
1-Row Coil
Airflow, CFM
600 1000 2000 2800
GPM Heating Capacity (MBH)
Waterside
Head Loss
(ft. wg.)
2 27.5 34.3 43.8 48.3 0.86
3 29.3 37.3 49.0 54.8 1.87
4 30.4 39.0 52.1 58.7 3.25
5 31.0 40.1 54.1 61.3 5
6 31.5 40.9 55.6 63.2 7.08
7 31.8 41.5 56.7 64.7 9.55
8 32.1 41.9 57.5 65.8 12.35
10 32.5 42.6 58.8 67.5 19
Air Side Pressure Drop (Inches WC)
0.02 0.04 0.14 0.24
Unit Size 112
2-Row Coil
Airflow, CFM
400 600 800 1400
GPM Heating Capacity (MBH)
Waterside
Head Loss
(ft. wg.)
2 28.1 34.8 39.8 49.6 1.15
3 29.9 37.7 43.8 56.1 2.50
4 30.9 39.4 46.0 60.0 4.35
5 31.5 40.5 47.5 62.6 6.68
6 32.0 41.2 48.6 64.5 9.49
7 32.3 41.8 49.4 65.9 12.79
9 32.8 42.5 50.4 67.9 20.79
10 32.9 42.8 50.8 68.6 25.46
Air Side Pressure Drop (Inches WC)
0.05 0.10 0.16 0.41
Unit Size 210
2-Row Coil
Airflow, CFM
500 800 1200 1800
GPM Heating Capacity (MBH)
Waterside
Head Loss
(ft. wg.)
1.5 32.3 40.0 46.4 52.3 0.33
3 37.6 48.8 59.1 69.6 1.27
4 39.1 51.6 63.4 75.8 2.21
5 40.2 53.4 66.3 80.0 3.41
6 40.9 54.7 68.3 83.1 4.85
7 41.4 55.7 69.9 85.5 6.55
9 42.1 57.0 72.1 88.8 10.65
10 42.4 57.5 72.9 90.1 13.09
Air Side Pressure Drop (Inches WC)
0.04 0.09 0.17 0.33
Unit Size 212
2-Row Coil
Airflow, CFM
600 1000 2000 2800
GPM Heating Capacity (MBH)
Waterside
Head Loss
(ft. wg.)
2 40.4 51.5 66.0 72.3 0.64
3 44.1 57.9 77.7 87.0 1.4
4 46.2 61.8 85.1 96.5 2.45
5 47.5 64.3 90.2 103.3 3.77
6 48.5 66.1 94.0 108.3 5.35
7 49.2 67.5 96.8 112.2 7.24
9 50.2 69.4 100.9 117.9 11.75
10 50.5 70.1 102.5 120.0 14.44
Air Side Pressure Drop (Inches WC)
0.04 0.09 0.29 0.51