Application
Point Databse Application 2920
44
Siemens Industry, Inc.
Application Note, App 2920
140-1307
2015-07-07
Point
Number
Descriptor
Factory
Default
(SI Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
{62}
CAL SUP VLV
NO
--
--
--
YES
NO
65
ROOM P GAIN
20.0 (36.0)
--
0.25 (0.45)
0
--
--
66
ROOM I GAIN
0.01 (0.018)
--
0.001 (0.0018)
0
--
--
{67}
UOC GEX MAX
1000 (471.9)
CFM
(LPS)
4 (1.8876)
0
--
--
{68}
UOC GEX MIN
500 (235.95)
CFM
(LPS)
4 (1.8876)
0
--
--
{69}
TOTL SUPPLY
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
70
SUP P GAIN
0.015
--
0.001
0
--
--
{71}
UOC SUP MAX
2200
(1038.18)
CFM
(LPS)
4 (1.8876)
0
--
--
{72}
UOC SUP MIN
220
(103.818)
CFM
(LPS)
4 (1.8876)
0
--
--
{73}
CTL STPT
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{74}
HOOD VOL
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
76
VOLUME STATE
1
--
1
0
--
--
{77}
DO 6
OFF
--
--
--
ON
OFF
{78}
CTL TEMP
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0 (8.88888)
--
--
{79}
TEMP LOOPOUT
400
PCT
0.4
0
--
--
{83}
VOL DIFFRNC
0 (-0.0001)
CFM
(LPS)
4 (1.8876)
-8000 (-3775.2)
--
--
{84}
AI 5
74.0
(23.496)
DEG F
(DEG C)
0.5 (0.28)
37.5 (3.056)
--
--
{85}
GEX FLO STPT
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
86
FAIL LIMIT
40 (18.876)
CFM
(LPS)
4 (1.8876)
0
--
--
{87}
CAL GEX VLV
NO
--
--
--
YES
NO
{88}
VOL DIF STPT
400
(188.7599)
CFM
(LPS)
4 (1.8876)
-8000 (-3775.2)
--
--
{89}
OTHER EXH
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
90
OC V ALM LVL
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
91
UC V ALM LVL
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--
{92}
VENT ALM
OFF
--
--
--
ON
OFF
{93}
SUP FLO STPT
0 (0.0)
CFM
(LPS)
4 (1.8876)
0
--
--