Data Sheet for Product

8
Siemens Industry, Inc.
A6V11402065_en
Smart Infrastructure
2020-07-30
Ambient conditions and protection classification
Classification per IEC/EN 60730
Function of automatic control devices
Pollution degree
Overvoltage category
Type 1
2
III
Design type Device suited for use with equipment of safety classes I
and II
Degree of protection of housing to IEC EN 60529
Room automation station
With terminal cover
IP20
IP30
Degree of protection of housing to EN 60529 IP55
Chemical resistance Exposed surfaces are chemically resistant to vaporized
hydrogen peroxide (VHP), formaldehyde, chlorine dioxide
(clidox), perchloric acid, soduium hypochlorite 3 - 6%
(bleach), quaternary ammonium 7% in 1:128 tap water
(ammonia).
Climatic ambient conditions:
Transport (packaged for transport) as per EN 60721-3-2
Operation as per EN 60721-3-3.
Class 2K3
Temperature -40...85 °C (-40... 185 F)
Air humidity 5...95%.
Class 3K5
Temperature 0...50 °C (32... 120 F)
Air humidity 5...95%.
Mechanical ambient conditions:
Transport as per IEC/EN 60721-3-2
Operation as per IEC/EN 60721-3-3
Class 2M2
Class 3M2
Standards, directives and approvals
Product standard EN61326
Electromagnetic compatibility For residential, commercial, and light industrial
environments.
EU conformity (CE) EN61326-1: 2013
AS/NZS 61000-6-8: 2012
BACnet BTL Listed, BACnet Application Specific Controller (B-
ASC)
BACnet Protocol Revision 13
Environmental compatibility The product environmental declaration contains data on
environmentally compatible product design and
assessments (RoHS compliance, materials composition,
packaging, environmental benefit, disposal).
Quality ISO 9001 (Quality)