Installation Instructions

Installation Instructions
Document No. 537-753
Rev. 3, February, 2000
Fume Hood Controller Enclosure
Page 1 of 2
Product Description
The Fume Hood Controller Enclosure is a general
purpose meal cabinet with a removable cover that
houses the Fume Hood Controller Board. The Fume
Hood Controller Enclosure is designed for a variety
of mounting configurations. The only restriction is
that the enclosure be securely fastened and
accessible for service.
Product Number
537-899
Required Tools
Medium-duty electric drill
1/2-inch (13mm) drill bit
Level
Marker
Medium flat-blade screwdriver
Prerequisites
Avoid mounting enclosure near large motors
or radio equipment.
Avoid mounting enclosure in an area where it
might be disturbed during normal
maintenance on the fume hood.
Maximum cable length between the controller
enclosure and the fume hood operator panel
is 50 feet (15m).
NOTE:
When mounting the enclosure, allow
adequate clearance the sides of the
enclosure in order to tighten the cover
screws.
Expected Installation Time
13 minutes
Instructions
1. Remove the enclosure cover.
2. Remove the appropriate conduit knockouts
(Figure 1).
Figure 1. Enclosure Dimensions and Knockouts.
3. On the wall or the surface on which you will
mount the enclosure, measure and mark a level
line 6 feet (1.8m) above the floor. See Figure 2.

Summary of content (2 pages)