Installation Instructions
Installation Instructions
Document No. 540-368
August, 2004
Differential Pressure Monitor
Item No.: 540-368 Rev. 030 Page 1 of 3
Product Description
The Differential Pressure Monitor (DPM) (Figure 1)
monitors and displays the differential pressure
between a room and an adjacent space. The DPM
also provides visual and audible alarms during
abnormal conditions. This kit contains:
• Differential Pressure Monitor with mounting
plate
• Three removable terminal blocks (wire
connectors)
• Four 5/8-inch slotted pan-head screws
• Two 3/8-inch tamper-resistant screws
• Two keys (w/p.n. 547-005 and 547-006)
Normal
Alarm
Horn
Silence
No Isolation/
Neutral
Infectious Isolation/
Negative Pressure
SWITCH OVERRIDE DOOR OPEN
HIGH PRESSURE LOW PRESSURE
GENERAL FAILURE ANTEROOM
NEGATIVE ISOLATION
PROTECTIVE ISOLATION
INFECTIOUS ISOLATION
NEGATIVE PRESSURE
POSITIVE PRESSURE
INCHES OF H
2
0
PRESSURE MODE KEY SWITCH
(OPTIONAL)
SEN0175R3
PORTABLE OPERATOR’S
TERMINAL PORT
NORMAL LED (GREEN)
ALARM LED (RED)
HORN SILENCE BUTTON
Figure 1. Differential Pressure Monitor.
Product Numbers
547-002 (without keyswitch)
547-005 (with keyswitch, negative pressurization)
547-006 (with keyswitch, positive pressurization)
Required Tools
• Small flat-blade screwdriver
• Medium flat-blade screwdriver
• 5/64-inch Allen-key wrench
• Wire strippers
• Volt-ohm meter
Expected Installation Time
26 to 30 minutes
Prerequisites
• Electrical box and plaster ring in place
• 24 Vac power cable in place
• Remote Pressure Transmitter(s) in place (to
prevent DPM from alarming when powered
up)
If using a Room Pressurization Controller (RPC):
• Pressure mode signal cable from the RPC to
the DPM in place
If DPM is to be connected to the System 600 via
a FLN:
• Local Area Network (FLN) cable from the
S600 field panel or FLN device to the DPM in
place
If using an external alarm or analog output:
• External alarm or analog output (4-20 mA
signal) cable in place
If using anteroom applications (Application 702
or 704):
• Constant Volume (CV) Controller pressure
mode signal cable in place