Installation Instructions

Document No. 570-112
Installation Instructions
June 14, 2013
Page 2 of 3 Siemens Industry, Inc.
WARNING
Do not proceed with these
installation instructions until the
fume hood has been cleaned and
emptied of all hazardous
substances including fumes,
vapors, toxic materials,
contaminants, chemicals, bacteria,
etc.
Expected Installation Time
30 minutes
Installation Instructions
Measuring the Sash Opening
1. Measure the length from the mounting surface to
the sash. Confirm that sensor extension length is
sufficient for installation.
2. With the sash window fully closed, mark the
location of the bottom of the sash window with
the marker.
3. With the sash window fully open, mark the
location of the bottom of the sash window with
the marker.
4. Measure the length between the open and
closed marks. Add 2 inches (5 cm) to account for
over-travel.
NOTE: For outside mounting: This measurement
must not exceed the mounting surface length
from Step 1.
Mounting the Sash Sensor
1. Locate the appropriate mounting area.
Figure 1: 546-04000 Mounting options.
Figure 2: 546-04001 Mounting Options.
- Mounting brackets can also be switched to
opposite side.
Figure 3: Bracket mounting.
2. To change measuring cable direction, remove
the bracket attaching screws and rotate sensor
body to desired direction.
Figure 4: Cable Direction.