Wiring Connections
Several electrical connections must be made from
the field panel, or UC to the terminal to operate the
AOP Transducers and the differential pressure
transmitter.
NOTE: The AOP Transducer used in these steps
is P/N 545-113.
1. Connect a two-conductor 20 AWG cable to
the field panel’s 0 to 10V output or UC’s
universal output. Connect it to the AOP
Transducer connected to the mixing damper
or through the wiring bushing/knockout on
the terminal enclosure (Figure 5) to the AO
P Transducer inside the enclosure. The wire
bushing can be removed and a standard
1/2-inch conduit knockout fitting may be
installed. Connect the cable to the AOP
Transducer (See Figure 6).
2. Connect a two-conductor 20 AWG cable to the
field panel’s 4 to 20 mA input or UC’s universal
input. Connect it to the differential pressure
transmitter (Figure 7) or through the wiring
bushing/knockout on the terminal enclosure
(See Figure 5) to the differential pressure
transmitter inside the enclosure. Connect the
cable to the differential pressure transmitter.
The installation is now complete.
Figure 6. AO-P Transducer Wiring Connections.
Figure 7. Differential Pressure
Transmitter
Wiring Connections.