Installation Instructions

Document No. 570-119
Installation Instructions
October 26, 2016
Siemens Industry, Inc. Page 3 of 13
3. Remove the controller from the static proof bag
and snap it into place on the mounting rail.
4. If the controller will be used with a field panel,
disconnect the field level network (FLN) trunk
from the field panel.
5. Wire the FLN trunk to the controller. After all
controllers are connected to the FLN, reconnect
the FLN trunk to the field panel.
6. If the controller requires Offboard Air Modules,
install them now following the appropriate
Installation Instructions (see
Product Numbers
).
7. Connect the point wiring (see
Wiring Diagram
s).
CAUTION
DO Wiring Each DO provides a
Normally Open (NO) terminal and a
Common (C) terminal.
To reduce noise and the potential
for ground loops, both connections
of a 24 Vac load must be wired
directly to the DO terminal on the
controller board.
Raccordement des sorties
numériques (DO) – chaque DO se
compose d’une borne normalement
ouverte (NO) et d’une borne
commune (C).
Afin de réduire les emissions
sonores et d’éviter de créer des
boucles de terre, les deux
connexions à une charge de 24 Vac
doivent être directement raccordées
à la borne DO sur la carte
contrôleur.
CAUTION
The fume hood flow module, the
FHC, any 0 to 10 Vdc actuator used
by the LCM, and the LCM cannot
share a single power trunk.
The preferred configuration for
shared power trunks is to use one
trunk for the FFM and FHC and
another trunk for the actuator(s) and
LCM.
Le module de débit de la hotte, le
FHC, et tout actionneur 0…10 Vdc
utilisé par le LCM, et le LCM ne
peuvent pas partager un même
tronc d’alimentation.
La configuration préférée pour des
troncs d’alimentation partagés
utilise un tronc pour the FFM et le
FHC, et un autre tronc pour le(s)
actionneur(s) et le LCM.
8.
Plug the room temperature sensor cable
into the RTS port.
9.
Connect the power trunk. DO NOT apply
power to the controller without first
consulting the specialist.