Commissioning Instructions

Before You Begin
Setting Controller Address
7
Siemens Industry, Inc. Start-up Procedures 140-1342
Restricted 2015-11-09
Setting Controller Address
1.
In WCIS, select
View > Edit/View Reports
.
2.
Select a report from the list and click
Apply
.
3.
Set CTLR ADDRESS to the BACnet MS/TP MAC address. (0 through 127 for
Master; 128 through 254 for Slave).
NOTE:
See the
WCIS Online Help
for instructions on auto-addressing on the network.
Otherwise, set the controller address and MS/TP network baud rate prior to
connecting the controller to the network. See
Configuring BACnet Parameters [➙ 17].
Setting the Application
1.
Add the controller to your job database and select the desired application.
6700 Slave Mode
6740 2-Position Constant Volume Fume Hood with Damper
At the start of the calibration cycle, the controller automatically sets CAL AIR to YES.
When the cycle is complete, CAL AIR returns to NO.
The air velocity sensor calibration cycle begins within three minutes of an application
start-up or initialization, depending on the controller’s address.
Setting Display Units
Set ENG UNITS to English or System International (SI) units (default is English units)
depending upon which unit (fpm or m/sec) you want displayed at the Operator Display
Panel.
NOTE:
All measurements entered during the start-up sequences may be entered as either
English or SI values (listed in parentheses after the English unit), depending upon
which unit has been selected using the Metric/English Units button on the appropriate
tool.
Testing the Operator Display Panel
Test the Operator Display Panel (ODP) as follows:
1. Set LAMP TEST to ON.
2. Verify that all visual display functions of the ODP appear and that the audible alarm
sounds continuously.
3. Set LAMP TEST to OFF.