Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Setting High Flow Setpoint
- Setting Low Flow Setpoint
- Setting ODP Display
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Damper Control
- Checkout of Damper
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Configuring BACnet Parameters
- Auto Discover and Auto Addressing
- Flashing Controller Firmware
Before You Begin
Verifying Power
6
Siemens Industry, Inc. Start-up Procedures 140-1342
Restricted 2015-11-09
CAUTION
A separate power supply is required if a 4-20 mA sensor is used.
Failure to follow wiring precautions will result in equipment damage.
Verifying Power
1.
Verify that the controller has 24 Vac power and that the fuse has been inserted
into the trunk or that power to the transformer is ON.
2.
Verify that the Basic Sanity Test (BST) LED on the controller flashes once per
second.
Verifying Slave Mode Application Number
1.
Plug the cable into the micro USB port.
NOTE:
Drivers for the ODP II port must be loaded to your computer prior to being
able to communicate with the ODP II. Drivers can be found on the Technical
Support Website.
2.
Verify that Application 6700 (Slave Mode) is running at the controller.