Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Setting High Flow Setpoint
- Setting Low Flow Setpoint
- Setting ODP Display
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Damper Control
- Checkout of Damper
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Configuring BACnet Parameters
- Auto Discover and Auto Addressing
- Flashing Controller Firmware
Before You Begin
Auto Discover and Auto Addressing
24
Siemens Industry, Inc. Start-up Procedures 140-1342
Restricted 2015-11-09
FIELDVAL
This value must be set to the FIELDID. The format of this data is specific to the ID.
Description
Acceptable Values
ObjectName 30 RAD50 characters
Instance 0 – 4194302
Description 60 ASCII characters
Location 60 ASCII characters
MaxMaster 1 – 127
Point numbers Depend on the specific points
MMIBaud 1200, 2400, 4800, 9600, 19200, 38400
MMIPriority 8 – 16
IsMetric 0 – No, 1 – Yes
IsSlave 0 – No, 1 – Yes
The Pre-Engineered Data file can be used in different ways. For example, you can
create a group or collection of information for every TEC. You can then assign the
correct group to the TEC based on the location as indicated by the job schedule. The
schedule will display the serial numbers for all TEC’s and the location where the TEC
was installed. The groups of data are set up for a specific location and you simply
select the correct group for the TEC that has the serial number associated with that
location.
You can also set up groups that contain information that must be set in multiple TEC’s.
Select all TEC’s that need the specific data and assign the ID.
Sample .csv file:
IDENTIFIER,FIELDID,FIELDVAL
Building100_TEC_VAV001,ObjectName,VAV in Building 100
Building100_TEC_VAV001,Instance,5400