Commissioning Instructions

Before You Begin
Auto Discover and Auto Addressing
23
Siemens Industry, Inc. Start-up Procedures 140-1342
Restricted 2015-11-09
You can configure values for multiple controllers with different applications by first
selecting and making changes to one controller and then selecting all controllers and
clicking
Configure.
NOTE:
Once you select multiple controllers with different applications the Application tab
goes blank. However, WCIS retains all changes and send the data for all selected
controllers.
.csv File Format
The .csv file is auto generated from CT (is the old manufacture installed output file) and
can be imported into WCIS. It has the following format and must be manually created.
First line must be IDENTIFIER, FIELDID, FIELDVAL; all additional lines will be data
in that format.
IDENTIFIER
This field is used to create groupings of data. Each group can be thought of as a
collection of information (configuration data and point initial values) that will be loaded
into one or more TEC’s. The groups cannot be subdivided into smaller collections.
FIELDID
This is the specific data that will be set. All configuration data will have a key word
associated with it and all points will be referenced by their point number (object ID).
The following is a list of fields:
ObjectName Sets the device object name.
Instance Sets the device instance number.
Description Sets the device description.
Location Sets the device location.
MaxMaster Sets the device max master.
MMIBaud Sets the baud rate of the MMI tool port.
MMIPriority Sets priority for P1 commands received through the MMI tool port.
IsMetric Sets the units to SI.
IsSlave Sets the unit to a MSTP slave device.
Comment Creates comments in the file to make it more readable and are not
imported into the tool.