Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Setting High Flow Setpoint
- Setting Low Flow Setpoint
- Setting ODP Display
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Damper Control
- Checkout of Damper
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Configuring BACnet Parameters
- Auto Discover and Auto Addressing
- Flashing Controller Firmware
Before You Begin
Auto Discover and Auto Addressing
21
Siemens Industry, Inc. Start-up Procedures 140-1342
Restricted 2015-11-09
Configuring Discovered Devices
Each device on the network must have unique identifiers in the following fields:
Address
Instance
Object Name - 30 alphanumeric character limit for Siemens field panels.
1. To change any of these fields, click in that field and enter the desired value.
2. When all fields are defined, click Configure.
All devices defined properly displays Addressed.
If a device has not been defined properly, it displays Unaddressed and the
problem field displays red text.
3. Correct any issues and click Configure.