Commissioning Instructions

Before You Begin
Auto Discover and Auto Addressing
20
Siemens Industry, Inc. Start-up Procedures 140-1342
Restricted 2015-11-09
Configuration Settings
Auto Address # Start - Beginning address number. An address is reserved for each
discovered device starting with this number.
Auto Instance # Start - Beginning instance number. An instance number is
reserved for each discovered device starting with this number.
Reassign Address and Instance drop-down menu - Reassigns the address and
instance number of the selected device(s).
Reassign Address Only drop-down menu - Reassigns the address of the selected
device(s).
Reassign Instance Only drop-down menu - Reassigns the instance of the selected
device(s).
Auto-Discovery
Find Unaddressed Device - Searches the connected network for all devices
(addressed and unaddressed).
Configure - Sends modified application data to the controller(s).
Read Relinquish Default - Refreshes relinquish default column of the Application
tab with values from the controller.
Revert to Import - Returns to Pre-Engineered Data after changes have been made.
Import Pre-Engineered Data - A .csv file can be used to set initial values in the
controller. The file can be taken from Commissioning Tool or exported from Excel.
See
Commissioning a Controller [➙ 22].
Auto-Discovery Procedure
Click Find Unaddressed Device.
If a NAM (Network Asset Manager) device is not defined, the NAM
Configuration window displays. All new TECs can be assigned as a NAM.
Enter the serial number (found on print from electrician).
Enter a unique (unused) address (0 through 127).
Click OK.
The device is assigned as the NAM for the network with the address you specified.
The NAM device auto-discovers all other devices on the network.
WCIS displays all devices.