Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Setting High Flow Setpoint
- Setting Low Flow Setpoint
- Setting ODP Display
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Damper Control
- Checkout of Damper
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Configuring BACnet Parameters
- Auto Discover and Auto Addressing
- Flashing Controller Firmware
Before You Begin
Auto Discover and Auto Addressing
19
Siemens Industry, Inc. Start-up Procedures 140-1342
Restricted 2015-11-09
Auto Discover and Auto Addressing
An improved commissioning workflow has been designed for all BACnet PTEC
controllers (standard 66
xx
applications) along with WCIS (Revision 4.0 and later). This
provides the option to use the MS/TP network (using the field panel or a router) and
the WCIS tool to discover and auto-address each controller. For more information, see
the
WCIS Online Help
.
NOTE:
The current workflow will continue to support setting the baud rate and address for
each controller using the HMI port or at the room unit.
All BACnet PTEC controllers (standard 66
xx
applications) have an internal unique
serial number and a two part serial number label.
1. Connect WCIS to the field panel or use a router connected to the MS/TP network.
2. Assign one PTEC a valid address (using the serial number). This will establish and
set the baud rate for the entire network.
Auto Discovery allows you to automatically discover and identify PTEC/ATEC
controllers on the BACnet MS/TP Network. There are two basic configurations:
Devices not configured with an address. (Devices are discovered by their unique
serial number.)
Devices configured with an address and available for modification.
Filtering
These buttons allow you to select what you see in the Auto-discovery window. All three
buttons are selected by default.
Unaddressed - Displays unaddressed devices
Failed - Displays failed devices
Addressed - Displays addressed devices