Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Setting High Flow Setpoint
- Setting Low Flow Setpoint
- Setting ODP Display
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Damper Control
- Checkout of Damper
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Configuring BACnet Parameters
- Auto Discover and Auto Addressing
- Flashing Controller Firmware
Before You Begin
Setting ODP Display
11
Siemens Industry, Inc. Start-up Procedures 140-1342
Restricted 2015-11-09
Setting ODP Display
Set ODP DISPLAY to the desired value. Values are CFM or MODE. In CFM, the ODP
displays the exhausted CFM. Use the table below to set the value. The default value is
MODE.
ODP
Display
Flow
Setpoint
Actual display
on the ODP
Cfm HI Cfm
Low Cfm
Mode HI
Low
Setting Hi and Low Warn Limits
Skip this step unless there is a special requirement on the job; the default will be used.
1.
Change report to
STARTUP
.
2.
Set HI WARN LMT and LOW WARN LMT.
These limits are defined as a percentage of the controlled setpoint, meaning
that the alarm limits will be closer as the EXH STPT decreases. The default
values are 135% and 85% respectively. These points may be adjusted to
meet customer requirements.
Setting Hi and Low Alarm Limits
Skip this step unless there is a special requirement on the job; the default will be used.
1.
Change report to
STARTUP
.
2.
Set HI ALM LMT and LOW ALM LMT.
These limits are defined as a percentage of the controlled setpoint, meaning
that the alarm limits will be closer as EXH STPT decreases.
The default values are 150% and 70% respectively. These points may be
adjusted to meet customer requirements.
Setting Alarm Timer
Skip this step unless there is a special requirement on the job; the default will be used.
Set ALARM TIME to a value of 1 through 255 seconds.
This is the time the flow must be in an alarm or warn condition before the alarm will
sound. The alarm clears immediately upon returning to normal operation. The
default for ALARM TIME is 5 seconds.