Basic Documentation
Table Of Contents
Technology Report
February, 2003
Siemens Industry, Inc. Page 1 of 6
VAV Fume Hood Energy Savings and Safety Considerations
Sash Closure vs. Automatic Face Velocity Setback
This report addresses the potential energy savings
and safety considerations associated with Variable
Air Volume (VAV) fume hood control systems that
offer automatic face velocity setback. Recall that the
purpose of a VAV fume hood control system is to
control fume hood exhaust as a function of the sash
opening in order to maintain a constant face velocity.
By maintaining a constant face velocity, fume hood
air consumption is reduced whenever the sash
opening is reduced, thereby saving ventilation
system energy. VAV fume hood air consumption and
ventilation system energy usage is minimized
whenever the sash is fully closed.
This contrasts with Constant Air Volume (CAV) fume
hoods, which do not change overall fume hood air
consumption in relation to the sash position. Thus,
CAV fume hoods consume significantly more
ventilation system energy than VAV fume hoods.
Automatic Face Velocity Setback
Aside from maintaining a constant face velocity at all
sash positions, some VAV fume hood control
systems incorporate a type of user detection sensor
to enable initiating an automatic reduction in face
velocity when the user is not at the fume hood. The
claim is made that when no one is at a fume hood, a
face velocity of 60 feet per minute (fpm) in lieu of the
commonly accepted 100 fpm will still provide
adequate fume containment. And subsequently, by
reducing the face velocity from 100 fpm to 60 fpm,
fume hood air consumption will be reduced to about
60% of what it would be at 100 fpm.
Safety Considerations
Before addressing the potential energy savings
claim, the safety issues associated with automatic
face velocity setback should be the first
consideration. Although face velocity setback has
been promoted for a number of years it continues to
be a subject of controversy within the laboratory
ventilation industry. The reservations against
implementing face velocity setback center around
whether 60 fpm will provide adequate fume
containment even if no one is in front of the fume
hood.
Research has revealed that room air currents or
cross currents in the vicinity of the fume hood can be
very detrimental to effective fume hood containment.
Even relatively mild air currents passing a fume
hood sash opening can draw out fumes from the
hood interior. Figure 1 illustrates chemical fumes
being d
rawn out of the fume hood by room air
currents (shown by dark arrows) passing the open
sash. This phenomenon can result when the room
air currents are horizontal, vertical, or even angular.
Thus, all room air currents pose the potential for
compromising effective fume hood containment.
ROOM AIR
ROOM AIR
ROOM AIR
ROOM AIR
FUME
FUME
FUME
F
U
M
E
ROOM AIR
ROOM AIR
Figure 1. Room Air Currents Can Draw Out
Fumes from the Interior of the Fume Hood.
Document No. 1
49- 976