4. Clean the mounting surface with the alcohol
towelette.
5. Peel the adhesive backing from the sensor
connector. Affix the connector to the fume hood
so that there is no tension and minimal slack on
the sensor and its attached wires.
6. Route the sensor wires between the fume hood
and the bottom of the airfoil, and to the
controller.
7. Secure the wires with the wire tie mounts and
nylon wire ties. Trim the wire ties with the wire
cutters.
8. If there are multiple sashes, use the wire marker
labels to number the end of the sensor wires.
See Figure 14 for proper sash numbering.
9. Bundle multiple wires together every 12 inches
(306 mm).
Inside sash UniTrak mount:
1. Remove the access panel on the inside wall of
the fume hood.
2. Drill a 3/8-inch hole through the inside wall of the
fume hood.
3. Insert the white plastic bushing in the 3/8-inch
hole.
4. Route the sensor wires through the hole, and fill
the bushing with the silicon in the white tube.
SeeFigure13.
ACCESS
PANEL
SENSOR
CONNECTOR
UNITRAK
SENSOR
INSIDE
WALL
OUTSIDE
WALL
PLASTIC
BUSHING
FUM0207R1
Figure 13. Routing Wires Through Fume Hood Wall.
5. Reach through the access panel opening
(between the inside and outside walls of the
fume hood) and plug the sensor connector into
the connector on the end of the wires leading
from the UniTrak sensor strip.
6. Route the wires between the inside and outside
walls, and to the controller.
7. Secure the wires with the wire tie mounts and
nylon wire ties. Trim the wire ties with the wire
cutters.
8. If there are multiple sashes, use the wire marker
labels to number the end of the sensor wires.
See Figure 14 for proper sash numbering.
9. Bundle multiple wires together every 12 inches
(306 mm).
The installation is now complete.
Figure 14. Sash Wire Numbering.