Application

Overview
BACnet
7
Siemens Industry, Inc. Application Note 140-1344
Restricted 2015-11-09
BACnet
The controller communicates using BACnet MS/TP protocol for open communications
on BACnet MS/TP networks.
Product
Supported BIBBs
BIBB Name
BTEC/PTEC DS-RP-B B Data Sharing-Read Property-B
DS-RPM-B Data Sharing-Read Property Multiple-B
DS-WP-B Data Sharing-Write Property-B
DM-DDB-B Device Management-Dynamic Device Binding-B
DM-DOB-B Device Management-Dynamic Object Binding-B
DM-DCC-B Device Management-Device Communication Control-B
DM-RD-B Device Management-Reinitialize Device-B
DM-BR-B Device Management-Backup and Restore-B
DM-OCD-B Device Management-Object Creation and Deletion-B
CPT Confirmed Private Transfer (Auto Discovery)
UPT Unconfirmed Private Transfer
Auto Discovery
Auto Discovery allows you to automatically discover and identify PTEC/ATEC
controllers on the BACnet MS/TP Network. There are two basic configurations:
Devices not configured with an address. (Devices are discovered by their unique
serial number.)
Devices configured with an address and available for modification.
Auto Addressing
Auto Addressing allows you to automatically assign device addresses to a
PTEC/ATEC controller on the BACnet MS/TP Network. If a controller is not configured
with a MAC address, you have the option to auto-address or manually address the
controller. During this time the baud rate is automatically detected by the controller.
Controller(s) must be connected on the BACnet/IP network in order for automatic
addressing to occur.