Application
Table Of Contents
- Overview
- Sequence of Operation
- Average Face Velocity Control
- AVS Calibration
- AO2 Flow Signal
- Control Loop - Damper Application
- Venturi Application
- Minimum Exhaust Mode
- Maximum Exhaust Mode
- Warning Limits
- Alarm Limits
- Alarm Output
- Horn Disable
- Sash Area Alarms
- Table Access Feature
- Emergency Mode
- Start-up/Decommission Mode
- Fail Mode
- Wiring Diagrams
- Point Database Application 6741
- Point Database Application 6742
Point Database Application 6742
37
Siemens Industry, Inc. Application Note 140-1344
Restricted 2015-11-09
Object
Type
Object
Instance
(Point
Number)
a)
b)
Object Name
(Descriptor)
Factory Default
(SI Units)
c)
Eng Units
(SI Units)
c)
Range
Active Text
Inactive
Text
(CM)
AO 66 VERT WIDTH2 0.0 (0.0) INCHES
(CM)
0-255.5 -- --
AO 67 VSASH HGHT1 0.0 (0.0) INCHES
(CM)
0-255.5 -- --
AO 68 VSASH HGHT2 0.0 (0.0) INCHES
(CM)
0-255.5 -- --
AO 69 TRACK HEIGHT 0.0 (0.0) INCHES
(CM)
0-255.5 -- --
AO 70 BYPASS HGHT 0.0 (0.0) INCHES
(CM)
0-255.5 -- --
AO {71} BYPASS OPEN 100 PCT 0-255 -- --
AO 72 FAIL AREA 0.0 (0.0) SQ. FT
(SQ M)
0-113.774298274 -- --
AO {73} EXTERNAL A 0.0 (0.0) SQ. FT
(SQ M)
0-113.774298274 -- --
AO 74 MAX EXT AREA 0.0 (0.0) SQ. FT
(SQ M)
0-113.774298274 -- --
AO 75 MIN EXTVOLTS 1 VOLTS 0-2.55 -- --
BO {78} CAL EXH VLV NO -- Binary YES NO
BO 79 EXH VLV STAT NOTCAL -- Binary NOTCAL CAL OK
AO {80} EXH MAX 3500 (1651.65) CFM (LPS)
0-16380 -- --
AO {81} EXH MIN 192 (90.6048) CFM (LPS)
0-16380 -- --
AO {82} EXH STPT 0 (0.0) CFM (LPS)
0-16380 -- --
AO {83} FVEL STPT 100 (0.508) FPM
(MPS)
0-4095 -- --
AO 84 OCC FV STPT 100 (0.508) FPM
(MPS)
0-4095 -- --
AO 85 UNOC FV STPT 90 (0.4572) FPM
(MPS)
0-4095 -- --
AO 86 OCC LOW FV 100 (0.508) FPM
(MPS)
0-4095 -- --
AO 87 OCC HIGH FV 100 (0.508) FPM
(MPS)
0-4095 -- --
AO 88 OCC DELAY 30 SEC 0-1023 -- --
AO {89} EXH SIG AO2 0 VOLTS 0-10.23 -- --
AO 90 AO2 RANGE 0 (0.0) CFM (LPS)
0-16380 -- --
AO 91 AO2 DEADBAND 5.2 PCT 0-102 -- --
AO 92 AO2 V MIN 1 VOLTS 0-10.23 -- --
BO {94} CAL AIR NO -- Binary YES NO