Application

Point Database Application 6742
36
Siemens Industry, Inc. Application Note 140-1344
Restricted 2015-11-09
Object
Type
Object
Instance
(Point
Number)
a)
b)
Object Name
(Descriptor)
Factory Default
(SI Units)
c)
Eng Units
(SI Units)
c)
Range
Active Text
Inactive
Text
AO 34 TRANS RANGE 0.0 (0.0) IN H2O (K
PA)
0-3.2767 -- --
AO 35 LINEAR FL RG 0 (0.0) CFM (LPS)
0-32764 -- --
AI {36} AVS2 PRESS 0.0 (0.0) IN H2O (K
PA)
0-3.2767 -- --
BI {37} DI 2 OFF -- Binary ON OFF
BI {38} DI 6 OFF -- Binary ON OFF
AO {39} AO 1 0 VOLTS 0-10.23 -- --
AO {40} EXH AO3 0 VOLTS 0-10.23 -- --
BO {41} DO 1 OFF -- Binary ON OFF
BO {42} DO 2 OFF -- Binary ON OFF
BO {43} DO 3 OFF -- Binary ON OFF
BO {44} DO 4 OFF -- Binary ON OFF
BO {45} DO 5 OFF -- Binary ON OFF
BO {46} DECOM DO6 OFF -- Binary ON OFF
BO {47} ALARM DO7 OFF -- Binary ON OFF
BO {48} AUTOZERO DO8 OFF -- Binary ON OFF
AI {49} AI 3 0 VOLTS 0-10.23 -- --
AI {50} AI 4 0 VOLTS 0-32.767 -- --
AI {51} AI 5 0 KOHM 0-327.67 -- --
AO {52} VERT SASH1 0.0 (0.0) INCHES
(CM)
0-16383.5 -- --
AO {53} VERT SASH2 0.0 (0.0) INCHES
(CM)
0-255.5 -- --
AO {54} FACE AREA 0.0 (0.0) SQ. FT
(SQ M)
0-113.774298274 -- --
AO {55} CAL SASH POS 0.0 (0.0) INCHES
(CM)
0-255.5 -- --
BO {56} CAL SASH LOC MIN -- Binary MAX MIN
AO {57} CAL SASH NUM 0 -- 0-255 -- --
AO {58} DMPR CMD -100 PCT -100-155 -- --
BO 60 AVS FAILMODE OPEN -- Binary OPEN HOLD
AO 61 EXH P GAIN 0.04 -- 0-4.095 -- --
AO 62 EXH I GAIN 0 -- 0-4.095 -- --
AO 63 EXH D GAIN 0 -- 0-4.095 -- --
AO 64 FIXED AREA 0.0 (0.0) SQ. FT
(SQ M)
0-113.774298274 -- --
AO 65 VERT WIDTH1 0.0 (0.0) INCHES 0-255.5 -- --