Application
Table Of Contents
- Overview
- Sequence of Operation
- Average Face Velocity Control
- AVS Calibration
- AO2 Flow Signal
- Control Loop - Damper Application
- Venturi Application
- Minimum Exhaust Mode
- Maximum Exhaust Mode
- Warning Limits
- Alarm Limits
- Alarm Output
- Horn Disable
- Sash Area Alarms
- Table Access Feature
- Emergency Mode
- Start-up/Decommission Mode
- Fail Mode
- Wiring Diagrams
- Point Database Application 6741
- Point Database Application 6742
Point Database Application 6741
34
Siemens Industry, Inc. Application Note 140-1344
Restricted 2015-11-09
Object
Type
Object
Instance
(Point
Number)
a)
b)
Object Name
(Descriptor)
Factory Default
(SI Units)
c)
Eng Units
(SI Units)
c)
Range
Active Text
Inactive
Text
AO 122 LO LIMIT 1 -- 0-2.55 -- --
BO 123 EMER DI6 OFF -- Binary ON OFF
AO {126} AVE FACE VEL 0 (0.0) FPM (MPS) 0-4095 -- --
BO {127} PPCL STATE EMPTY -- Binary LOADED EMPTY
a)
Points not listed are not used in this application.
b)
Point numbers that appear in brackets { } may be unbundled at the field panel.
c)
A single value in a column means that the value is the same in English units and in SI units.