Application

Sequence of Operation
Table Access Feature
23
Siemens Industry, Inc. Application Note 140-1344
Restricted 2015-11-09
Sash area alarms alert you when the sash area is above set limits. There are limits for
both attended and unattended modes of operation. The controller uses the following
points to perform this function:
DI2, ATTN.UNATTN, SASH TONE, UN ALRT AREA, AT ALRT AREA, OPEN TIME,
and SASH OP ALRT. ATTN.UNATTN is controlled by DI2, and when the DI is opened
the controller changes to ATTN mode.
When the DI is shorted, the controller changes to UNATTN mode.
ATTN MODEWhen in ATTN mode and the FACE AREA is larger than AT ALRT
AREA, the SASH OP ALRT point is turned on and the ODP horn beeps six times
every minute until the sash area is lowered below the AT ALRT AREA limit. The
horn beeping feature may be removed in ATTN mode by turning off the SASH
TONE point. When the FACE AREA is less than the AT ALRT AREA, the SASH
OP ALRT turns off and the ODP horn no longer beeps.
By pressing the horn silence button, you may stop the beeping for the time shown
in OPEN TIME.
UNATTN MODEWhen in UNATTN mode and the FACE AREA is larger than UN
ALRT AREA, the SASH OP ALRT point is turned on and the ODP horn beeps six
times every minute until the sash area is lowered below the UN ALRT AREA limit.
When the FACE AREA is less than the UN ALRT AREA, the SASH OP ALRT turns
off and the ODP horn no longer beeps.
Table Access Feature
The table access feature allows the controller to store values that are set once and left
alone, used infrequently or not accessed by the network.
These values are accessed using V TABLE PT. It will access the points TABLE FLOW
and TABLE VOLTS. For more information see the
Start-up Procedures for Application
6741 and Application 6742
.
Emergency Mode
The emergency mode operation overrides any other control mode in the Fume Hood
Controller. When the Emergency Purge button on the ODP is pressed, the following
sequence of events occurs.
1.
EMER ALM turns ON at BACnet priority level 1, the horn sounds, and the red
LED on the ODP illuminates. The ODP displays “EMERGENCY” mode and
indicates to close the hood.
2.
The Fume Hood Controller commands the damper/Venturi valve to fully open
for the time (in seconds) specified in EMER TIMER.
3.
After EMER TIMER has timed out, the Fume Hood Controller controls the flow
at the flow setpoint, EXH STPT, multiplied by the emergency set point
percentage, EMER STPT.
4.
When the Emergency Purge button is pressed a second time, the Fume Hood
Controller returns to normal operation for the current conditions.