Application

Point Database Application 6740
16
Siemens Industry, Inc. 140-1341
Restricted 2015-11-09
Point Database Application 6740
Object
Type
Object
Instance
(Point
Number)
a)
b)
Object Name
(Descriptor)
Factory Default
(SI Units)
c)
Eng Units
(SI Units)
c)
Range
Active Text
Inactive
Text
AO 1 CTLR ADDRESS 99 -- 0-255 -- --
AO 2 APPLICATION 6700 -- 0-32767 -- --
BO {05} LOW ALM OFF -- Binary ON OFF
BO {06} HIGH ALM OFF -- Binary ON OFF
BO {07} EMER ALM OFF -- Binary ON OFF
BO {08} GEN FAILURE OFF -- Binary ON OFF
AO {10} HI ALM LMT 150 PCT 0-255 -- --
AO {11} HI WARN LMT 135 PCT 0-255 -- --
AO {12} LOW WARN LMT 85 PCT 0-255 -- --
AO {13} LOW ALM LMT 70 PCT 0-255 -- --
AO {14} EMER TIMER 300 SEC 0-1023 -- --
AO {15} EMER STPT 150 PCT 0-255 -- --
BO {16} LOW WARN OFF -- Binary ON OFF
BO {17} HIGH WARN OFF -- Binary ON OFF
AO {18} ALARM TIME 5 SEC 0-255 -- --
BO {19} ALM AKNLG OFF -- Binary ON OFF
BO {20} OCC.UNOCC OCC -- Binary UNOCC OCC
AO {21} STARTUP MODE 3 -- 0-255 -- --
BO {22} ODP STPT SW HI -- Binary LO HI
BO {23} RIGHT SWITCH OFF -- Binary ON OFF
AI {31} EXH VOL 0 (0.0) CFM (LPS) 0-32764 -- --
AO {32} FLOW COEF 0.73 -- 0-2.55 -- --
AO {33} DUCT AREA 0.55 (0.051106) SQ. FT (SQ
M)
0-6.375 -- --
AO {34} TRANS RANGE 0.0 (0.0) IN H2O (K PA) 0-3.2767 -- --
AO {35} LINEAR FL RG 0 (0.0) CFM (LPS) 0-32764 -- --
AI {36} AVS2 PRESS 0.0 (0.0) IN H2O (K PA) 0-3.2767 -- --
BI {37} DI2 STPT SW HI -- Binary LO HI
BI {38} DI 6 OFF -- Binary ON OFF
AO {39} AO 1 0 VOLTS 0-10.23 -- --
AO {40} AO 3 0 VOLTS 0-10.23 -- --
BO {41} EXTN DO1 HOLD -- Binary EXTN HOLD