Commissioning Instructions

Table Of Contents
Before You Begin
Verifying Slave Mode Application Number
7
Siemens Industry, Inc. Start-up Procedures 140-1345
Restricted 2015-11-09
Verifying Slave Mode Application Number
1.
Plug the cable into the micro USB port.
NOTE:
Drivers for the ODP II port must be loaded to your computer prior to being
able to communicate with the ODP II. Drivers can be found on the Technical
Support Website.
2.
Verify that Application 6700 (Slave Mode) is running at the controller.
Setting Controller Address
1.
In WCIS, select
View > Edit/View Reports
.
2.
Select a report from the list and click
Apply
.
3.
Set CTLR ADDRESS to the BACnet MS/TP MAC address. (0 through 127 for
Master; 128 through 254 for Slave).
NOTE:
See the
WCIS Online Help
for instructions on auto-addressing on the network.
Otherwise, set the controller address and MS/TP network baud rate prior to
connecting the controller to the network. See
Configuring BACnet Parameters [➙ 34].
Setting the Application
1.
Add the controller to your job database and select the desired application.
6700 Slave Mode
6741 with 2 Vertical Sash Sensors with Damper
6742 with 2 Vertical Sash Sensors with Venturi Air Valve
At the start of the calibration cycle, the controller automatically sets CAL AIR to YES.
When the cycle is complete, CAL AIR returns to NO.