Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Changing Exhaust Minimum
- Changing Exhaust Maximum
- Changing Face Velocity Setpoints and OCC Delay
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Remote Purge
- Fume Hood Specific Sash Setup and Calibration
- Setting External Face Area Input
- Setting Sash Area Alarms
- (Optional) Setting Damper Control — Application 6741
- Checkout of Damper — Application 6741
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting Airflow Control — Application 6742
- Range of Airflow Control – Application 6742
- Configuring Airflow Control - Application 6742
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Configuring BACnet Parameters
- Auto Discover and Auto Addressing
- Flashing Controller Firmware
Before You Begin
Auto Discover and Auto Addressing
39
Siemens Industry, Inc. Start-up Procedures 140-1345
Restricted 2015-11-09
Import Data
1. Click the Import Pre-Engineered Data button.
The Import Configuration Data dialog box displays.
2. Browse to the desired .csv file and click Open.
The imported files are listed in the Pre-Engineered Data section of the Auto-
Discovery window.
Each line in the window is a grouping of data for a controller. For more information see
.csv File Format [➙ 39].
Assigning Import Data to Controller
1. Click in the Import ID column of the desired controller in the devices section.
2. Select the appropriate Import ID number of the Pre-Engineered Data you want to
assign.
The Application and Configuration tabs are updated with the new (Pre-Engineered)
data. You can manually change/update any data.
Assigning Import Data to Multiple Controllers
1. Click on the desired Import Data from the list in the Pre-Engineered Data section.
2. Select all desired controllers in the Devices window.
3. Right-click the selection in the Devices window and then select Assign Import Data
from Import ID x.
4. Click Configure.
The Application will load into each controller selected. The Application and
Configuration tabs are updated with the new (Pre-Engineered) data.
Commissioning Multiple Controllers
If you’re commissioning multiple controllers with the same application all values can be
loaded to each controller selected.
You can select multiple controllers by holding down either the SHIFT or CTRL key and
clicking on multiple controllers listed.
You can configure values for multiple controllers with different applications by first
selecting and making changes to one controller and then selecting all controllers and
clicking
Configure.
NOTE:
Once you select multiple controllers with different applications the Application tab
goes blank. However, WCIS retains all changes and send the data for all selected
controllers.