Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Changing Exhaust Minimum
- Changing Exhaust Maximum
- Changing Face Velocity Setpoints and OCC Delay
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Remote Purge
- Fume Hood Specific Sash Setup and Calibration
- Setting External Face Area Input
- Setting Sash Area Alarms
- (Optional) Setting Damper Control — Application 6741
- Checkout of Damper — Application 6741
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting Airflow Control — Application 6742
- Range of Airflow Control – Application 6742
- Configuring Airflow Control - Application 6742
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Configuring BACnet Parameters
- Auto Discover and Auto Addressing
- Flashing Controller Firmware
Before You Begin
Auto Discover and Auto Addressing
38
Siemens Industry, Inc. Start-up Procedures 140-1345
Restricted 2015-11-09
Configuring Discovered Devices
Each device on the network must have unique identifiers in the following fields:
Address
Instance
Object Name - 30 alphanumeric character limit for Siemens field panels.
1. To change any of these fields, click in that field and enter the desired value.
2. When all fields are defined, click Configure.
All devices defined properly displays Addressed.
If a device has not been defined properly, it displays Unaddressed and the
problem field displays red text.
3. Correct any issues and click Configure.
Commissioning a Controller
Learning the Application Point Team
Once a device has been addressed, select your application.
Do one of the following:
– Right-click in the Application column and select the desired Application.
– Click Configure to load the device for your application.
– Right-click on the controller and select Learn Point Team Descriptor.