Commissioning Instructions

Table Of Contents
Before You Begin
Auto Discover and Auto Addressing
36
Siemens Industry, Inc. Start-up Procedures 140-1345
Restricted 2015-11-09
Filtering
These buttons allow you to select what you see in the Auto-discovery window. All three
buttons are selected by default.
Unaddressed - Displays unaddressed devices
Failed - Displays failed devices
Addressed - Displays addressed devices
Configuration Settings
Auto Address # Start - Beginning address number. An address is reserved for each
discovered device starting with this number.
Auto Instance # Start - Beginning instance number. An instance number is
reserved for each discovered device starting with this number.
Reassign Address and Instance drop-down menu - Reassigns the address and
instance number of the selected device(s).
Reassign Address Only drop-down menu - Reassigns the address of the selected
device(s).
Reassign Instance Only drop-down menu - Reassigns the instance of the selected
device(s).
Auto-Discovery
Find Unaddressed Device - Searches the connected network for all devices
(addressed and unaddressed).
Configure - Sends modified application data to the controller(s).
Read Relinquish Default - Refreshes relinquish default column of the Application
tab with values from the controller.
Revert to Import - Returns to Pre-Engineered Data after changes have been made.
Import Pre-Engineered Data - A .csv file can be used to set initial values in the
controller. The file can be taken from Commissioning Tool or exported from Excel.
See
Commissioning a Controller [➙ 38].