Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power
- Verifying Slave Mode Application Number
- Setting Controller Address
- Setting the Application
- Setting Display Units
- Testing the Operator Display Panel
- Setting Duct Area
- Setting Airflow Sensing Input
- Setting Flow Coefficients
- Automatic Calibration Option
- Setting Blank Display
- Setting Display Weight
- Setting Display Resolution
- Changing Exhaust Minimum
- Changing Exhaust Maximum
- Changing Face Velocity Setpoints and OCC Delay
- Setting Hi and Low Warn Limits
- Setting Hi and Low Alarm Limits
- Setting Alarm Timer
- Setting Emergency Setpoint
- Setting Emergency Timer
- Setting Remote Purge
- Fume Hood Specific Sash Setup and Calibration
- Setting External Face Area Input
- Setting Sash Area Alarms
- (Optional) Setting Damper Control — Application 6741
- Checkout of Damper — Application 6741
- (Optional) Setting Airflow Input Type
- (Optional) Calibrating the DP Transmitter without an Autozero Module
- (Optional) Calibrating with an Autozero Module
- AVS FAILMODE
- Setting Airflow Control — Application 6742
- Range of Airflow Control – Application 6742
- Configuring Airflow Control - Application 6742
- Setting AO2 Range
- Setting AO2 Voltage Minimum
- Start-up/Decommission Mode
- Loop Tuning Procedures
- Configuring BACnet Parameters
- Auto Discover and Auto Addressing
- Flashing Controller Firmware
Before You Begin
Configuring BACnet Parameters
34
Siemens Industry, Inc. Start-up Procedures 140-1345
Restricted 2015-11-09
Calculating Average Face Velocity
Configuring BACnet Parameters
Using WCIS, do the following:
1. From the Device menu, select Device Properties to configure BACnet parameters.
2. In the Object section, enter information for the following fields:
– Instance Number – unique to BACnet network (valid values are 0 through
4,194,303).
– Object Name – unique to BACnet network (30 alphanumeric character limit in
RAD50).
– Device Description – description of controller (60 alphanumeric character limit).
– Device Location – physical location of controller (60 alphanumeric character
limit).
3. In the BACNet Communication Settings section:
– Set the CIS/MMI Command Priority to the desired value.
– Set Baud Rate to the MS/TP network baud rate. Options are; 9600, 19200,
38400 or 76800.
4. In the MSTP Slave section do one of the following:
– Check the MS/TP Slave check box if the controller is to function as a slave
device (when address range is 0 through 127).
– Set the Max Master Node number.