Commissioning Instructions

Table Of Contents
Before You Begin
Configuring BACnet Parameters
34
Siemens Industry, Inc. Start-up Procedures 140-1345
Restricted 2015-11-09
Calculating Average Face Velocity
Configuring BACnet Parameters
Using WCIS, do the following:
1. From the Device menu, select Device Properties to configure BACnet parameters.
2. In the Object section, enter information for the following fields:
Instance Numberunique to BACnet network (valid values are 0 through
4,194,303).
Object Name unique to BACnet network (30 alphanumeric character limit in
RAD50).
Device Descriptiondescription of controller (60 alphanumeric character limit).
Device Locationphysical location of controller (60 alphanumeric character
limit).
3. In the BACNet Communication Settings section:
Set the CIS/MMI Command Priority to the desired value.
Set Baud Rate to the MS/TP network baud rate. Options are; 9600, 19200,
38400 or 76800.
4. In the MSTP Slave section do one of the following:
Check the MS/TP Slave check box if the controller is to function as a slave
device (when address range is 0 through 127).
Set the Max Master Node number.