Application
Point Database Application 2923
36
Siemens Industry, Inc.
Application Note, App 2923
140-1347
2015-07-07
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
109
FAIL TIME
60
SEC
2
0
--
--
110
MTR SETUP
0
--
1
0
--
--
{111}
SUP DMP POS
0
PCT
0.4
0
--
--
112
MTR1 TIMING
95
SEC
1
0
--
--
113
MTR1 ROT ANG
90
--
1
0
--
--
{114}
GEX DMP POS
0
PCT
0.4
0
--
--
115
MTR2 TIMING
95
SEC
1
0
--
--
116
MTR2 ROT ANG
90
--
1
0
--
--
117
MINHOODVOLTS
1
VOLTS
0.01
0
--
--
{118}
RM CO2
1000
PPM
1
0
--
--
125
SUP MAX RATE
0 (0.0)
FPM (MPS)
1 (0.00508)
0
--
--
126
GEX MAX RATE
0 (0.0)
FPM (MPS)
1 (0.00508)
0
--
--
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.