User`s manual

14
SIEMENS (S5 COMMUNICATIONS) REFERENCE
Display Screen
Parameter for:
16-Bit Unsigned Integer,
8-Bit Unsigned Integer,
16-Bit Signed Integer &
16-Bit BCD Data Description
Register Number The PLC data location operand and address.
Digits Right of Decimal The number of digits to be placed to the right of the
decimal.
Digits Left of Decimal The number of digits to be placed to the left of the decimal.
Leave Place for Sign (Y or N) Leave a one character place for the polarity sign (+ or -)
when the data is displayed.
Show Leading Zeros (Y or N) Display any zeros to the left of the data.
Minimum Register Value The minimum data value of the PLC location.
Maximum Register Value The maximum data value of the PLC location.
Minimum Displayed Value The minimum data value to be displayed. This value is
displayed when the data in the PLC location is equal to the
minimum register value.
Maximum Displayed Value The maximum data value to be displayed. This value is
displayed when the data in the PLC location is equal to the
maximum register value. The range defined by the
Minimum Displayed Value and the Maximum Displayed
Value is proportionally scaled to the range of the minimum
and maximum register values. If both ranges are equal
then the scaling ratio is 1:1.
Minimum Bar Value (Bar Graph Only) The minimum value of data to be
displayed in the Bar Graph. This value must be greater or
equal to the Minimum Displayed Value.
Maximum Bar Value (Bar Graph Only) The maximum value of data to be
displayed in the Bar Graph. This value must be less than or
equal to the Maximum Displayed Value. The Minimum and
Maximum bar graph values may be used to display a
particular range or window of an overall range (Minimum
and Maximum Displayed Values).