User`s manual
SH-300 Text Panel
Page 76 of 103
4.15 KDN-K3 Series
SH-300 can communicate with KDN-K3 series PLC, the communication port is the programming
port of PLC
SH-300 software configuration:
Item Content
SH-300 COM port 9 pin COM port
PLC COM port Programming port
Default parameter 9600bps、8bits、1stop、None
Station No. 1-31,1 is Windows default
Distance (Max.) 15m
Communication mode RS232
Cable type Special cable
Inner relay address I0.0-I7.7/ Q0.0-Q7.7/ M0.0-M31.7
Register address AIW0-62/AQW0-62/AQW0-4094
Connection guidance of Special cable:
SH-300 side
2 RXD
2 RXD PLC side
9 pin D shape 3 TXD 3 TXD 9 pin D shape
Female plug Male plug
5 GND 5 GND
( when SH-300 communicates with KDN-K3 series PLC you are recommended to use the
programming cable )