4.13 Emerson EC20 Series
SH-300 can communicate with Emerson EC20 series PLC, before communication with SH-300
PLC need to be configured .setup port0 of PLC as Modbus communication protocol.
SH-300 software configuration:
Item Content
SH-300 COM port 9 pin COM port
PLC COM port Programming port
Default parameter 19200bps、8bits、1stop、Even
Station No. 0-255,1 is Windows default
Distance (Max.) 15m
Communication mode RS232
Cable type Special cable
Inner relay address M0-M1999 Y0-Y377(O)
Register address D0-D7999 T0-T255
Please consult Emerson PLC user manual for particular address
Connection guidance of Special cable
2 RXD 4RXD
SH-300 side
3 TXD 5TXD
PLC side
9 pin D shape 8pin Round shape
Female plug male plug
5 GND 3 GND
(when SH-300 communicates with Emerson EC20 series PLC you are recommended to use the
programming cable )
The picture for 8 pin Round shape
Female plug