SH-300 User’s Manual Contents Contents 1 SH-300 Hardware part..................................................................................................... 3 1. 1 1. 2 1. 3 1. 4 1. 5 System General Introduction............................................................................... 3 Specification Parameter....................................................................................... 3 Hardware Structure...............................................................................
SH-300 Text Panel 3. 4 3. 5 3. 6 System Password................................................................................................57 Data setting.......................................................................................................... 58 State Monitoring...................................................................................................59 4 Connection with PLC.....................................................................................................
SH-300 User’s Manual Hardware Part SH-300 Hardware part 1 1.1 System General Introduction SH-300 is a small Human-Machine interface, mainly being used to be connected with PLC or other intelligent controllers with COM port communication function. It can monitor, setup and modify the data of the register or the status of the relay inside the PLC; thereby manipulators can monitor conveniently the PLC or the running status of the intelligent controllers with COM port communication function.
SH-300 Text Panel Brightness 60 cd/m2 Color Monochrome(yellow-green) Contrast Adjustable resistor Background light Long life yellow-green LED Memory 110KB Flash ROM Communication Port PC RS232& PLC RS485/422 & PLC RS232 Function button 14 freely configurable keys Allowable power disruption ≤20ms Frame Dimension 171.8 x 84.2 x 38.6mm Display Dimension 97.0 x 34.
SH-300 User’s Manual Hardware Part key are system keys. Except the basic function, the other fourteen keys can be set as special function keys to realize the Screen-jumping and digital setup functions. The front of panel of SH-300 programmable text display is shown as follows: Left key Up key 4.3’’ STN LCD Display Right key Down key ESC-ESC key 0-9 digital key SET-Set key +/- sign ENT-enter key CLR Deletion ALM-alarm key Basic function of keys: setting the input value of the PLC registers.
SH-300 Text Panel When using if the contrast of the LCD isn’t fit, revolve the contrast potentiometer on the left side with small sized screwdriver till the contract reach the desired degree The display of SH-300 is with LED background light. Press any key, the background light will be turned on automatically. The backlight will be turned off automatically if there is no operation in the minutes .Users can modify the turnoff time of the background light in SH300 software and then download into SH-300.
SH-300 User’s Manual Hardware Part 1.4 Function Key List key Function [←] When modifying the register data, the cursor will be moved one-digit left. [→] When modifying the register data, the cursor will be moved one-digit right. [↑] [↓] To jump to the previous screen, whose number is set in the screen property option. (The default value is the current number 1.) In data-setting mode, pressing it, the modified number will be plus 1.
SH-300 Text Panel 1.5 Installation Dimensions and Guide Dimensions of SH-300 (L*W*H): 171.8×98.8×38.6 (Unit: mm) Dimensions of the installation hole: 165×85 (Unit: mm) Method 1: Embedded installation The installment surface must be up to Standard Type 4, being applicable for indoor or the switchboard box on coequal condition. Thickness of Clapboard: 0.5-0.9 mm.
SH-300 User’s Manual Hardware Part Method 2:DIN rail installation(standard 35mm DIN rail installation) Method 3: Screw installation (To install on the motherboard) Page 9 of 103
SH-300 Text Panel 《Memo》 ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ———————————————————————————— ———————————————————————————— —— Page 10 of 103
SH-300 User’s Manual Software Part SH300 Software Part 2 2.1 SH300 General Introduction SH300 is the special development software of SH-300 Programmable Text Display, which is run on the base of WINDOWS 98/2000/XP platform. SH300 software makes the best use of the abundant graphic interface and the object-faced design of WINDOWS, which makes it convenient for the users edit the required control screens and the alarm interfaces in a short time. The essential of the project file is the Screen.
SH-300 Text Panel 2.3 Installation and Uninstallation of SH300 2.3.1 Installation of SH300 The installation of SH300 is very simple. In the installation process, a prompting dialogue box will appear automatically and you will complete the installation smoothly on the computer under its guidance. The main steps are as follows: 1. Insert the SH300 software CD into the CD Driver. Select the installation program file Setup.
SH-300 User’s Manual Software Part 3. Fulfill the interface with the correct information and click NEXT to enter the installation path setting interface as follows: ▲ Click NEXT, the SH300 software will be installed in the default path as shown. If it is necessary to select the path, click BROWSE to reset the desired path. ▲Click Back, it will return to the previous interface. ▲Click Cancel, it will exit the installation program. 4.
SH-300 Text Panel Note: Selection of Typical option is recommended. 5. Select NEXT to enter the program aggregate displaying window as in the following diagram: ▲ Click Next to start the installation program; ▲ Click Back to return to the previous interface; ▲ Click Cancel to terminate the installation program. 6. The installation program proceeds to the automatic installation procedure. Click Cancel, if you want to terminate now. 7.
SH-300 User’s Manual Software Part 2.3.2 Uninstallation of SH300 There are two ways for the uninstallation of SH300: 1. Remove from WINDOWS START MENU ▲ Under the WINDOWS taskbar, click Start→Program→ARRAY→SH300→Unistall of SH300 As shown in the following diagram: ▲ When a confirm uninstall dialogue box appearing, click Yes and the following remove interface will appear. 2.
SH-300 Text Panel 2.4 Operation Interface The window of SH300 software is mainly made up of menu bar, tool bar, distribution bar, edit section, window description section, status bar and property section.
SH-300 User’s Manual Software Part Indicator: displaying on/off status of PLC inner middle relay Function key: 14 keys on SH-300 panel being able to be defined as function keys, whose functions are screen-jumping and switch control etc. Static text, including Chinese characters, English characters and characters from other operation system Dynamic text, text content being able to be changed by PLC’s register.
SH-300 Text Panel 2.4.1 File This instruction is mainly used for project file management, including creating, opening, saving etc Menu Name Function New project Create a new project file Open project Open an old project file Save project Save the current project file Save as Close project Exit Save the current file to a new path Close the current project file Exit SH300 software 2.4.
SH-300 User’s Manual Software Part Menu Name Cut Function Cut components Copy Copy components Paste Paste components Delete Delete components Select All Select all components Control Change the arrangement Position Set alignment type Save Screen Bitmap Save the current screen as graph format Show Back Dot (G) Display 2.4.3 View This instruction is to display the toolbar, distribution bar and the status bar.
SH-300 Text Panel ▲ Positionbar: Distribution bar displaying instruction ▲ Statusbar: Status bar displaying instruction 2.4.4 Screen This instruction mainly includes new screen, delete screen, copy screen, set screen No., SH300 config and alarm list. Menu Name New screen Function Create a new screen Delete screen Delete the current screen Copy screen Copy the current screen Set screen No.
SH-300 User’s Manual Software Part Caution! The maximal number of the screen is 256. 2.4.5 Object The instruction mainly includes Lamp, Touch Key, Static Text, Dynamic Text, Numeric, Process Bar, Trend Line, Picture and Message Display. Menu Name Lamp Function Displaying on/off status of PLC inner middle relay Touch button 14 keys defined as function keys, which being used to realize the screen-jumping, switch control and so on functions.
SH-300 Text Panel Progress Bar Trend Line Picture Message Display Bar graph, which can be used to monitor data change in PLC Trend graph, which can be used to monitor data change in PLC Insert the monochrome graphics file (Max. 192×64 pixels ) Displays the status of PLC inner relay user-definedly. 2.4.6 Connect The instruction is mainly used to Set PLC type, Set Communication Port and Download Data.
SH-300 User’s Manual Software Part ▲ User-defined Immanent resource: to re-define the relative information of each interface in SH-300. 2.4.8 Help The menu mainly includes SH300 software version No. and other information.
SH-300 Text Panel 2.5 Operation Instruction (Mitsubishi FX Series as an example) 2.5.1 Indicator Click “Lamp” option under “Object” menu or click in toolbar, there will be a dashed rectangular frame following and moving together with the mouse. Move the mouse to the proper position in the edit section and then click the left button of the mouse to confirm, and there will be one indicator in the edit section.
SH-300 User’s Manual Software Part Positive Logic 0 Negative Logic 1 Negative Logic 0 In positive logic, if the corresponding middle relay is ON, the indicator will be solid; and if the corresponding middle relay is OFF, the indicator will be hollow. In negative logic, if the corresponding middle relay is ON, the indicator will be hollow; and if the corresponding middle relay is OFF, the indicator will be solid. 2.5.
SH-300 Text Panel Screen-Jumping: Action of the key is defined as screen-jumping function. Register Set: Action of the key is defined as register parameter setup function. ▲Coil The number, type and address correspond to the definition of PLC inner relay. ON: to set the designated relay to be ON. OFF: to set the designated relay to be OFF. Reverse: Press this key, the value of the designated relay will be reversed. ▲ Style Double: The displaying picture of the indicator will be double.
SH-300 User’s Manual Software Part 2.5.4 Dynamic text Click “Dynamic Text” option under “Object” menu, or click in toolbar, there will be a dashed rectangular frame following and moving together with the mouse. Move the mouse to the proper position in the edit section and then click the left button of the mouse to confirm, and there will be one indicator in the edit section.
SH-300 Text Panel If the value of D100 is 60, the “motor speed is normal” will be displayed as follows: If the value of D100 is 80, the “motor speed is too rapid” will be displayed as follows: 2.5.5 Register Click “Register” option under “Object” menu, or click in toolbar, there will be a dashed rectangular frame following and moving together with the mouse.
SH-300 User’s Manual Software Part ▲ Position Property: X Position: specifying the horizontal position of the component Y Position: specifying the vertical position of the component Note: The grid origin is at the top left corner of the screen. ▲ Style Double: The register will be double relatively. Reverse: The register and the background color will be reversely displayed. ▲ Format Set the digits, decimal digits and the display mode of the register data.
SH-300 Text Panel Caution! There may be some error in the conversion because of the limit of the operation precision of the floating number. For example: Design requirements: Screen 2 is two groups of the main property parameter of the related PLC, the rotate speed of principal axis and the rotate speed of the countershaft. The left column is the set value and the right column is the actual value.
SH-300 User’s Manual Software Part 2.5.6 Bar Graph Click “Bar Graph” option under Object” menu,click in toolbar, there will be a dashed rectangular frame following and moving together with the mouse. Move the mouse to the proper position in the edit section and then click the left button of the mouse to confirm, and there will be one indicator in the edit section.
SH-300 Text Panel This bar graph can be used to monitor the data in register D0. If the bar graph is fully displayed, it means the value in register D0 is 100. And when the bar graph is 20% displayed, it means the value in register D0 is 20. 2.5.7 Trend Graph Click “Trend Graph” option once with left button of mouse of menu “Object”, or click once in toolbar, there will be a dashed rectangular frame following and moving together with the mouse.
SH-300 User’s Manual Software Part ▲ Size Set the height and width of the trend graph. ▲ Display Full amount: 100% trend line will display the corresponding register value Empty amount: 0% trend line will display the corresponding register value Date dots: the total sample number in the whole trend line from left to right. The more the number is, the trend line will be more fine and the time will be longer. Sample interval: the interval between two neighboring sample dots.
SH-300 Text Panel ▲ Position Property: X Position: specifying the horizontal position of the component Y Position: specifying the vertical position of the component Note: The grid origin is at the top left corner of the screen. ▲ Size To adjust the height and width of the bitmap ▲ Reverse The color of the picture and the background will be reversely displayed. Note: SH300 software can support many kinds of graphic files, such as *BMP, *ICO, *JPG etc. 2.5.
SH-300 User’s Manual Software Part ▲ Position Property: X Position: specifying the horizontal position of the component Y Position: specifying the vertical position of the component Note: The grid origin is at the top left corner of the screen. ▲ Coil Property Station number, type and the address correspond to the type of PLC relay. ▲ Style Font: the type and size of displayed message are changeable. Reverse: the background color will be reversely displayed.
SH-300 Text Panel Each project file of SH-300 can set a group of alarm list information. And each piece of information corresponds to a relay. The definition numbers of all the relays are continuous. And the first addresses of all the relays are set by the users according to the actual program. If any relay changing from OFF to ON means the relative alarm is produced, and now the SH-300 will prompt the alarm displaying screen automatically and the alarm information will be displayed in the first row.
SH-300 User’s Manual Software Part When SH-300 is working normally, if there is any failure alarm or M0 and M2 are ON, the flashing alarm screen will prompt automatically on SH-300 as in the following: If the alarm failure is not corrected, the failure alarm information will flash and be displayed on SH-300. If the failure is corrected, the SH-300 will resume normal display. If the system is in examination and repair, user can check the failure alarm records via the “ALM” key on the panel.
SH-300 Text Panel Click “default” and then doubt click “message” on the left column.
SH-300 User’s Manual Software Part Modify the coordinate position Modify the text In this property frame, user can modify the X and Y coordinate position of the menu information (at the top left corner, it is the original coordinate position (0, 0) of X and Y) and the contents of the text information of the text frame (supporting multi language system). If “Default” is selected, which means the default interface will be displayed when communication.
SH-300 Text Panel The password set interface includes “LOGIN”, “LOGOUT”, “ESC EXIT” (default information). If the text of the information in the screen need to be changed and the position need not to be changed, cross “user menu setting” check box and doubt click the text needed to be changed, the following prompting frame will be displayed as the following: In the above property frame, the text information contents can be modified in the text frame (supporting multi language system).
SH-300 User’s Manual Software Part Example: Substitute the text “ENTER” for “LOGIN”, “QUIT” for “LOGOUT” and “RETURN” for “EXIT”. Click “OK”, the following diagram will be displayed. Click the “Input password” submenu, then the password input interface will be displayed as in the following diagram.
SH-300 Text Panel Example: substitute the text “password” for “Input password”, modify the position X to 0 and the position Y is fixed. Click “OK”, the following diagram will be displayed: Click the “Login OK” submenu, then the password being successfully input interface will be displayed as in the following diagram: In this interface, there are two lines of texts “Login Success”, “Press any key” (default information).
SH-300 User’s Manual Software Part In this property frame, user can modify the X and Y coordinate position of the menu information (at the top left corner, it is the original coordinate position (0, 0) of X and Y) and the contents of the text information of the text frame (supporting multi language system). If “Default” is selected, which means the default interface will be displayed when communication.
SH-300 Text Panel In this property frame, user can modify the X and Y coordinate position of the menu information (at the top left corner, it is the original coordinate position (0, 0) of X and Y) and the contents of the text information of the text frame (supporting multi language system). If “Default” is selected, which means the default interface will be displayed when communication.
SH-300 User’s Manual Software Part In this interface, there are two lines of texts “LOGOUT SUCCESS”, “PRESS ANY KEY” (default information).
SH-300 Text Panel If the text and the position of the information in the screen need to be changed, cross “user menu setting” check box and double click the text frame “NO ALARM INFORMATION”, the following prompting frame will be displayed as the following: In this property frame, user can modify the X and Y coordinate position of the menu information (at the top left corner, it is the original coordinate position (0, 0) of X and Y) and the contents of the text information of the text frame (supporting mu
SH-300 User’s Manual Software Part Note: After the modification of the self-defined information menu, click “Save” button and close the information frame, and write the edited program into SH-300, then the modified self-defined information will be written into SH-300. 2.7 Multi Language Editor SH300 provides completely open multi language menu structure, which provides user with completely self-defined menu.
SH-300 Text Panel ※Display Message: to display the message menu; ※Modification Message: to modify the message menu; ※Note Bar: in find function, the relative message after finding will be displayed in the bar. Click “language” menu, the pulldown menu is shown as the following, including “Open Language File”, “Save language File’’, “Close Language File” and “Exit”. Take a text as an example to introduce the operation of the SH300 Langeditor.
SH-300 User’s Manual Software Part 2.8 Operation Example Subject: The Drying Boxes Control System Control requirements: (1)Via SH-300 to monitor the work status of three groups of heating units; ( 2 ) Via SH-300 to observe the actual temperature and change the preset temperature of the drying boxes; (3)Via SH-300 to observe the actual speed and change the preset speed of the motor; (4)Via SH-300 to set alarm information of abnormal work; Operation Procedure: 1.
SH-300 Text Panel 3. Make Screen 2 “Temperature Setting” Click “New Screen” or icon, the following dialogue frame will be displayed: Correctly select “2” as the screen number, input the screen description “Temperature Setting”,select “1” as the up-jumping screen number and select “3” as the down-jumping screen number as in the following diagram: Press “OK” key to confirm and enter Screen 2.
SH-300 User’s Manual Software Part Select “Register” under “Object” menu or click in the tool bar. Move the mouse to proper place under “Current” and click the left key of the mouse to confirm. Then set the parameter of the register, Address=D1, Digits=4, Decimal=2, Mode=Dec. Don’t select the “Set” check box. Then place the text “℃” on its right as shown in the following diagram: 4. Make Screen 3 “State Monitoring” As stated above, create the Screen 3.
SH-300 Text Panel Select “Indicator” under “Object” menu or click in the tool bar. Move the mouse to proper place behind “Heating Unit 1” and click the left key of the mouse to confirm as in the following diagram. And add two other indicators as the above. Set the “Indicator” one by one.
SH-300 User’s Manual Software Part Select “Register” under “Object” menu or click in the tool bar. Move the mouse to proper place under “Current” and click the left key of the mouse to confirm. Then set the parameter of the register, Address=D90, Digits=5, Decimal=1, Mode=Dec. Don’t select the “Set” check box as shown in the following diagram: 6. Make Screen 5 “Alarm List” Click in the tool bar. A prompting dialogue frame as the following will be show. Set the initial coil type as M88 first.
SH-300 Text Panel Click “OK” to confirm. Thus the whole control file of the drying box system is finished. Then click “Save Project “ 7. Download the drying box project data into SH-300.
SH-300 User’s Manual Software Part 《Memo》 ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— Page 55 of 103
SH-300Text Panel 3 Manipulation 3.1 Download Window 1. Connect the operating unit interface to the configuration computer using a SH-PC cable. 2. Confirmed SH-300 has added on the DC24V power source. 3. Press and start to download the date, the screen appears the downloading picture prompt frame. Note : Don’t cut off the power supply when SH-300 is receiving data from the configuration computer. 3.
SH-300 User’s Manual Manipulation 3.3 Shifting the windows Take the project windows of the drying boxes as an example to introduce the manipulation of SH-300. SH-300 displays window No.1 at first (the initial window is No.1). Window No.1 is a main menu window. Pressing ① switch to the window of temperature setting(No.2) that is shown as follows: 3.4 System Password After setting system password, you must input the password before you change the data.
SH-300Text Panel Input the password (0-999999), which is shown as”*”. Press ENT. If password is correct, it will show the window as follows: If password is incorrect, it will show the window as follows: Then press ENT,return to the password window. Select “2 ,LOGOUT” and Press ENT it will show the window as follows: 3.5 Data setting When SH-300 display NO.
SH-300 User’s Manual Manipulation 3.6 State Monitoring After finished the setting of register, press “∧” and return to the main menu ,SH-300 is shown as follows: Press ② enter the window of state monitoring (No.3), which is shown as follows: SH-300 will display the state monitoring window for three group heating units. When a heating unit is running the indicator will be show as full state and operator can monitor the running state of the heating units by the window.
SH-300Text Panel 《Memo》 ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— Page 60 of 103
SH-300 User’s Manual Connection with PLC 4 Connection with PLC 4.1 Mitsubishi FX Series SH-300 can communicate with the programming port of all types of Mitsubishi FX series PLC or the FX2N-422BD module of the FX2N series. SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port/ FX2N-422BD Default parameter 9600bps、7bits、1stop、Even Station No. 1(1 is fixed and can’t be changed) Distance (Max.
SH-300 Text Panel 4.2 Siemens S7-200 Series SH-300 can communicate with the programming port or external communication port of Siemens S7-200 series through PPI protocol. SH-300 software configuration: Item Content SH-300 COM port RS485 COM port PLC COM port Programming port/ external communication port Default parameter 9600bps、8bits、1stop、Even Station No. 2-126 ,2 is Windows default Distance (Max.
SH-300 User’s Manual Connection with PLC 4.3 OMRON C Series SH-300 can communicate with the programming port of CQM 、 CPM series PLC through HOST-Link protocol. SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port/ external communication port Default parameter 9600bps、7bits、2stop、Even Station No. 0-99 ,0 is Windows default Distance (Max.) 15m Communication mode RS232 Cable type Special cable Inner relay address IR200.0-IR231.F(IR2000.
SH-300 Text Panel 4.4 Delta DVP Series SH-300 can communicate with the delta DVP series PLC, the communication port is the programming port of PLC SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 9600bps、7bits、1stop、Even Station No. 1-254 ,1 is Windows default Distance (Max.
SH-300 User’s Manual Connection with PLC 4.5 Panasonic FP Series SH-300 can communicate with Panasonic FP series PLC, the communication port is the programming port of PLC or external communication port. SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 9600bps、8bits、1stop、0dd Station No. 1-32 ,1 is Windows default Distance (Max.
SH-300 User’s Manual Connection with PLC 4.6 Vigor VH Series SH-300 can communicate with Vigor VH series PLC, the communication port is the Programme device assistant port of PLC SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 19200bps、7bits、1stop、Even Station No. 0-255 ,0 is Windows default Distance (Max.
SH-300 User’s Manual Connection with PLC 4.7 Koyo S Series SH-300 can communicate with Koyo S series PLC, the communication port is the programming port of PLC SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 9600bps、8bits、1stop、0dd Station No. 1-99 ,1 is Windows default Distance (Max.
SH-300 Text Panel 4.8 ADC DL05 Series SH-300 can communicate with ADC DL05 series PLC, the communication port is the programming port of PLC., In order that the SH300 can communicate with ADC DL 05 series communication Port2 normally, ADC PLC must be correspondingly configured. To do this, the ADC Communication Protocol must be defined with the DirectSoft software, Select the “SETUP” submenu under “PLC” option in the DirectSoft ,Set up Communication Ports according to the picture indicated below.
SH-300 User’s Manual Connection with PLC Connection guidance of port 1 special cable: SH-300 side 2 RXD 3 RXD 9 pin D shape Female plug 3 TXD 4 TXD PLC side 5 GND 1 GND (6PIN port1) ( when SH-300 communicates with ADC DL05 series PLC you are recommended to use the the programming cable ) Page 69 of 103
SH-300 Text Panel 4.9 FATEK FBs Series SH-300 can communicate with FATEK FBs series PLC the communication port is the port 0 of PLC SH-300 software configuration: Item Content SH-300 COM port PLC COM port 9 pin COM port Programming port Default parameter Station No. 9600bps、7bits、1stop、Even 1-254 ,1 is Windows default Distance (Max.) 15m Communication mode RS232 Cable type Special cable Inner relay address M0000-M2001 Register address R0000- R3839.
SH-300 User’s Manual Connection with PLC 4.10 Schneider NEZA/TWIDO Series SH-300 can communicate with Schneider NEZA/TWIDO Series PLC through Modbus RTU protocol, the communication port is the programming port of PLC SH-300 software configuration: Item Content SH-300 COM port RS485 COM port PLC COM port Programming port Default parameter 19200bps、8bit、1stop、Even Station No. 1-247,1 is Windows default Distance (Max.
SH-300 Text Panel 4.11 AB (AB-DF1 protocol) Series SH-300 can communicate with the Allen-Bradley series PLC via AB-DF1 Protocol, the communication port is the programming port of PLC SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 9600bps、8bits、1stop、None Station No. 1 (1 is fixed and can’t be changed) Distance (Max.
SH-300 User’s Manual Connection with PLC 4.12 THINGET XC Series SH-300 can communicate with THINGET XC series PLC, the communication port is the programming port of PLC SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 19200bps、8bits、1stop、Even Station No. 0-255,1 is Windows default Distance (Max.
SH-300 Text Panel 4.13 Emerson EC20 Series SH-300 can communicate with Emerson EC20 series PLC, before communication with SH-300 PLC need to be configured .setup port0 of PLC as Modbus communication protocol. SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 19200bps、8bits、1stop、Even Station No. 0-255,1 is Windows default Distance (Max.
SH-300 User’s Manual Connection with PLC 4.14 HITACHI MICRO-EH Series SH-300 can communicate with HITACHI MICRO-EH series PLC, the communication port is the programming port of PLC SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 19200bps、7bits、1stop、Even Station No. 0 (0 is fixed and can’t be changed) Distance (Max.
SH-300 Text Panel 4.15 KDN-K3 Series SH-300 can communicate with KDN-K3 series PLC, the communication port is the programming port of PLC SH-300 software configuration: Item Content SH-300 COM port 9 pin COM port PLC COM port Programming port Default parameter 9600bps、8bits、1stop、None Station No. 1-31,1 is Windows default Distance (Max.) 15m Communication mode RS232 Cable type Special cable Inner relay address I0.0-I7.7/ Q0.0-Q7.7/ M0.0-M31.
SH-300 User’s Manual Connection with PLC 4.16 MODBUS RTU/ASCII and RTU/ASCII EXTEND protocol 1. Introducing Modbus Protocol SH-300 communicates by using a master–slave technique, in which one SH-300(the master) can send query message. one programmable controller(the slave) responds according to the requested data supplied by SH-300. The Modbus protocol establishes the format for the master’s query by placing into it the device address, a function code, any data to be sent, and error–checking field.
SH-300 Text Panel 4.
SH-300 User’s Manual Connection with PLC Note: 1. When selecting “3x” as register address type, single or double register only can be read, not to be written. 2. When selecting “4x” as register address type to read or write double register. the first byte contains the high order bit and the second contains the low order bit. 3. When selecting “5x” as register address type to read or write double register. The first byte contains the low order bit and the second contains the high order bit. 4.
SH-300 Text Panel When SH-300 set coil 15 the data format to be send from SH-300 is shown as following. Field Name Query message Example (Hex) Device address Function code Coil address Hi Coil address Lo Set data Hi Set data Lo CRC Lo CRC Hi 05 0C 0F FF 00 - The query message specifies the coil to be set. The requested ON/OFF state is specified by a constant in the query data field. A value of FF 00 hex requests the coil to be ON. A value of 00 00 requests it to be OFF.
SH-300 User’s Manual Connection with PLC 6.2.3. Here is an example of displaying and setting Register R1088 According to “the list of corresponding relationship between the address type and function codes in Modbus Protocol” the address type of reading and writing holding register is “4X” ,The holding register address is in the range of R0-R3839. Modbus address is in the range of 0-3839. the corresponding Modbus data address of register R1088 is 1088.
SH-300 Text Panel 4.17 SH-300 Freedom Protocol 1. Communication configuration SH-300 can communicate with some controllers via freedom protocol. When SH-300 communicates with controller via this protocol user need to define own controller freedom communication format first. Here SH-300 is a master, controller is a slave. The request message is sent from SH-300 and controller makes response message.
SH-300 User’s Manual Connection with PLC If Registers are addressed starting at B1, W1,DW1.
SH-300 Text Panel 3. The data format of query from SH-300 and response from PLC When SH-300 communicates with controller via freedom protocol the Register data and the status of inner coils can be set up by SH-300 and displayed on the SH-300 at real time. PC can be taken as dummy controller to communicate with SH-300. Here PC displays not only the Register data and the status of inner coils but also the data PC receives and sends during communicating with SH-300.
SH-300 User’s Manual Connection with PLC When reading coil M25 status the data format of query message from SH-300 and response message from controller is shown as following: Byte NO.
SH-300 Text Panel When writing coil M25 status the data format of query message from SH-300 and response message from controller is shown as following: Byte Query format (controller receive) Example Response format (controller Example NO.
SH-300 User’s Manual Connection with PLC 7. Read double Register DW(0X46) Use this function code to read the value of double Registers in controller. The query message specifies the Register starting address. Registers are addressed starting at zero: Register 0 is addressed as 0. Each Register data in the response message occupy two byte. The first byte contains the high order bits and the second contains the low order bits. Here is an example reading the value of Register 35 36 a.
SH-300 Text Panel Here is an example of writing 2A6B8C9D hex into two Registers 58.59 in controller a. Make the screen displayed as the following: b. Connect SH-300 with PC, download the screen into SH-300. c. click“ ”enter into simulation mode write 2A6B8C9D hex into two registers 58.
SH-300 User’s Manual Connection with PLC Here is an example of reading alarm list coil M1-M8 status (M0 is the lowest coil) a. Make the alarm list displayed as the following: b. Use function key to set coil M1.M2.M3.M8 ON and others OFF. c. Connect SH-300 with PC d. Click“ ”enter into simulation mode Description: The status messages of coil M1-M8: [0E][01] Coil No. M7 M6 M5 M4 M3 M2 M1 Coil status 0 0 0 0 1 1 1 data 0 E Coil No.
SH-300 Text Panel 4.18 Array FAB Series PLC SH-300 can communicate with Array FAB series PLC, and the communication port is the programming port of PLC. SH-300 software configuration: Item SH-300 COM port PLC COM port Default parameter Station No. Distance (Max.
SH-300 User’s Manual Connection with PLC Example 2: The operation of reading the input/output and the output status of the function block in FAB program. Example3: The operation of writing the status of output port (Only the empty port is writable.) Example4: Read the analog value and the parameter of the function block in FAB program.
SH-300 Text Panel FAB program is shown above. If there is a need to set and display the value of the function block B1 through SH-300, the operation is shown as following graph: Explanation: As the SH-300 can not identify second, minute and hour when it is displaying and setting the time of function block, the static text can be used firstly to input the unit that needs to be displayed (e.g. s m h).
SH-300 User’s Manual Connection with PLC 4.19 Array SR Series PLC SH-300 can communicate with Array SR series PLC, and the communication port is the programming port of PLC. SH-300 software configuration: Item SH-300 COM port PLC COM port Default parameter Distance (Max.
SH-300 Text Panel UP/DOWN Counter UDCT analog comparator CMPR Input analog IN ON Delay TOND OFF Delay TOFD Single pulse generator PONS Clock pulse generator BLNK Garph bar Holding-ON-delay relay MTOD UP/DOWN Counter UDCT analog comparator CMPR Dynamic text Input analog IN UP/DOWN Counter UDCT The number of corresponding function block in program: (0~127) The number of corresponding function block in program: (0~127) 0~7 The number of corresponding function block in program: (0~127) The number of cor
SH-300 User’s Manual Connection with PLC 4.20 Array APB Series PLC SH-300 can communicate with ARRAY APB series PLC, and the communication port is PLC programming port. SH-300 Software Configuration: Item SH-300 COM port PLC COM port Default parameter Communication distance(Max.) Communication mode Cable type Content 9 pin COM port Programming port 9600bps、8bits、1stop、none 15m RS232 APB-CP The description of address types used in SH300 software: No.
SH-300 Text Panel Write 4 DW DW0~DW255 BR BR0.0~n~BR31 9.0~n Timer 0 indicates the running value of the function block; 1 indicates the first set parameter value of the function block; 2 indicates the second set parameter value of the function block; n indicates the nth set parameter value of the function block; Read register value Read the parameter value of the function block in APB program.
SH-300 User’s Manual Connection with PLC 2.Modify the parameter value of function block B0011. a. In APB program, the value of the register DW10 is referenced as the off-delay time for the function block B0011, and the value of the register DW11 is referenced as the hold-ON time. The unit for the register value is millisecond. b. Click to set off-delay time for the function block B0011, and the address is DW10.
SH-300 Text Panel c. Click to set permanent light time for the function block B0011, and the address is DW11. The default unit for register value is Millisecond, which can be set as Second with 3 decimals.
SH-300 User’s Manual Connection with PLC 3. As B0012 is a function block of count type, is selected as the function object to read the current value. It is shown as following graph: a. Click to read current value of the function block B0012, and the address is BR12.0. b. In program, the property pin is connected with DW0 , the value of DW0 can be read by SH-300 4.Modify parameter value of the function block B0012. a.
SH-300 Text Panel Page 100 of 103
SH-300 User’s Manual Connection with PLC 4.21 Array TC-Pro Series Digital Timer/Counter/Tachometer SH-300 can communicate with Array TC-Pro Series digital timer/counter/tachometer through communication port. SH-300 software configuration: Item SH-300 COM port PLC COM port Default parameter Station No. Distance (Max.
SH-300 Text Panel 《Memo》 ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— ————————————————————————————— Page 102 of 103
SH-300 User’s Manual Appendix Appendix : Note item All basic default function keys except ALM, SET, ESC, ENT, UP, DOWN key can be redefined . If the default function conflict with the defined function, the basic function will be out of action. Setting register, press CLR key to enter desired digits. When only a single digit need to Change, move the cursor to the digit with the direction key and then input the number your need directly.