Specifications
4 Communication settings and guide of HMI connecting with controller
◎Supported Device
Device Bit Address Word Address Format Notes
UPSSet
UPSSet1-6
------ DDDDD
UPSPanel
UPSPanel0-9
------ DDDDD
UPSData
------
UPSData0-70
DDDD
UPSDisp
------
UPSDisp0
DDDDD
UPSCommand
------
UPSCommand0-52
DDDDD
UPSText
------
UPSText0-1
DDDDD
Slave driver notes:
1. Transmit the device value to LW, LB by timer; refer to the addr table for details.
2. UPSCommand must use with UPSSet、macro;
3. UPSDisp must use with UPStexr、UPSPanel、macro.
Epower HMI project notes
:
1. The project must have UPSData0 device, otherwise the data accuracy will be affected; Suggest to
put UPSData0 device in the public window.
2. LW.B indicates the bits of UPSData
◎Cable Diagram
COM0 connect to ups communication board
2 TXD
3 RXD
7 GND
Controller terminal
25 pin D-SUB (male)
HMI terminal
9pin D-SUB female/male
com2
3 TX
2 RX
5 GND
8 TX
7 RX
5 GND
com0
COM1 connect to King software or com debug tool
- 85 -