Specifications

4 Communication settings and guide of HMI connecting with controller
Series CPU Link Module COMM Type Parameter Cable
Danfoss FC-300 RS485 on the CPU unit RS485-2 Setting Your owner cable
Modbus RTU FC-300 RS485 on the CPU unit RS485-2 Setting Your owner cable
Communication Setting
Danfoss Protocol:
Modbus RTU Protocol:
Note
Change the value of 8-30 to 2 on the Danfoss inverter for modbus protocolChange the value of 8-30
to 0 for the Danfoss Protocol
Inverter
8-3* FC Port Setting
8-30 protocol
*[0] FC (danfoss protocol)
[2] Modbus (modbus protocol)
8-31 address
1 – 247 * 1 (HMI station No.)
- 64 -