Specifications
4 Communication settings and guide of HMI connecting with controller
NOTE:
1、When setting the parameter of ADDR, it match the PLC Station Number .
2、If connecting many devices, you should set different ADDR values.
YuDian AI 4_Loop
AI-7048
Device
Bit Address
Word Address(参数代号)
Format
Notes
HiAL 0.0-3.0 ------ D.D Read only
LoAL
0.0-3.0
------
D.D
Read only
dHAL
0.0-3.0
------
D.D
Read only
dLAL 0.0-3.0 ------ D.D Read only
orAL 0.0-3.0 ------ D.D Read only
AL1 0.0-3.0 ------ D.D Read only
AL2
0.0-3.0 ------
D.D Read only
PV
------
0.0-3.0
D.D
Read only
MV ------ 0.0-3.0 D.D
SV
------
0.0-3.0
D.D
ALARM ------ 0.0-3.0 D.D Read only
Reference ------ 0.0-3.086 D.DDD
Address correspond to AI
parameters code
NOTE:
1
、When setting the parameter of ADDR, it match the PLC Station Number.
2
、If connecting many devices, you should set different ADDR values.
3
、AI-7048 has 4 loops, so it occupies 4 address, For instance, Addr=5,address 5~8 were used by this
controller, other controller can’t use address 5~8.
EXAMPLE
Take HIAL for example, look up table and then know that HIAL parameters code is 1, so HIAL for 4
channels correspond to address in HMI should be Reference0.01,Reference1.01,Reference2.01,
Reference3.01.
If station number is 2, Reference0.01 is HIAL address of channel 2(station No. 2 + main address 0),
Reference1.01 is HIAL address of channel 2(station No. 2 + main address 1), and so on.
Thereinto the setting of station number is very important, it denotes start address of the controller (viz.
instrument address in instrument parameter), and main address just denotes 4 channels. When main address
is 0, it denotes channel (station number+0)
TABLE
Table 1
Parameter
Code
Adjustor Inspection instrument
DEC
AI-518/708/808/518P/70
8P/808P
AI-519/719/719P AI-501/701 AI-702M/704M/706M
0 SV /SteP SV /SteP N/A N/A
- 373 -