Specifications

4 Communication settings and guide of HMI connecting with controller
Index Register ------ V_word 1~64 DD
File Register ------ B_word 1~256 DD
Data Register ------ D_word 1~256 DDD
Cable Diagram
RS232 communication cable
Yokogawa programming cable
Controller terminal
6
pin
com
2
3
TX
2
RX
5
GND
8
TX
7
RX
5
GND
com
0
/
com
1
HMI terminal
9
pin D
-
SUB female
/
male
1
TXD
2
RXD
5
GND
RS485-4 communication cable
HMI terminal
9pin D
-SUB female/
male
1 RX-
6 RX
+
5 GND
SDA-
SDB
+
FG
RDA-
RDB+
4 TX-
9 TX
+
Controller
RS422 terminal
com0
/com1
RS485-2 communication cable
com0/com1
HMI terminal
9pin D-SUB female/male
Controller
RS422接线端
1 RX-
6 RX+
5 GND
SDA-
SDB+
FG
RDA-
RDB+
Ethernet communication protocol cable
Cross-connection or crossover network cable can be used as communication cable via the hub
Refer to
4.3 Download by Network Ethernet for method of making connection cable.
4.84 YuDian AI
Serial Communication
Series CPU Link Module Driver
- 371 -