4 Communication settings and guide of HMI connecting with controller
NOTE:
1. If you use MT5-S7-300 adapter to communicate, the baudrate of PLC must be 187.5K, and HMI must be
19.2K
2. If we use PC adapter, PLC station No. is not necessary, so the communication is one-to-one.
3. DB block must be created, otherwise the relevant registers can not write (DB.DBX, DB.DBW, DB.DBD).
DBm.DBW, DBm.DBD address start must be an even number.
PLC Setting
1. Production of the adapter with KINCO, MPI transmission rate must be set 187.5K. 19.2K general users
of the transmission rate, if the S7-300 MPI-side transmission rate is 19.2K, you need to change it into the
Siemens adapter 187.5K (where changes in the hardware properties)
2. MPI address must be 2.