Specifications
4 Communication settings and guide of HMI connecting with controller
com0/com1
HMI terminal
9pin D-SUB female/male
1 RX-
6 RX+
5 GND
4Tx-
7Tx+
3GND
1Rx-
2Rx+
4 TX-
9 TX+
Controller terminal
8pin Mini DIN(male)
2. FX
□□-485-BD communication
com0/com1
Controller
RS
422 terminal
HMI terminal
9pin D
-
SUB female/male
1 RX-
6 RX+
5
GND
SDB
SDA
SG
RDB
RDA
4 TX-
9 TX+
Q Series RS232 Cable
1. CPU port communication
com0
/com1
HMI terminial
9pin D-SUB female/male
2 RX
3 TX
2 TXD
1 RXD
5 GND 3 GND
Controller
6pin Mini DIN(male)
com2
7 RX
8 TX
5 GND
2. C24 module communication
Controller terminal
9 pin D-SUB (male)
com2
3 TX
2 RX
5 GND
8 TX
7 RX
5 GND
com0/com1
HMI terminal
9pin D-SUB female/male
3 TXD
2 RXD
5 GND
1 DCD
4 DTR
6 DSR
7 RTS
8 CTS
Q02U Series RS232 Cable
CPU port communication
- 223 -